Summary of Contents for elsner elektronik KNX T-L-Pr-UP Touch

  • Page 1 KNX T-L-Pr-UP Touch Presence, brightness and tempe- rature sensor Item numbers 70850 (pure white), 70852 (deep black) Installation and Adjustment...
  • Page 3: Table Of Contents

    7.9.1. AND logic 1+2 and OR logic outputs 1+2 ..........32 7.9.1.1. Block ....................33 7.9.1.2. Monitoring ..................34 7.10.AND logic connection inputs ................34 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensor KNX T-L-Pr-UP Touch Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 4 Contents 7.10.1. Connection inputs of the OR logic ............. 35 Elsner Elektronik GmbH • Sohlengrund 16 • 75395 Ostelsheim • Germany Sensor KNX T-L-Pr-UP Touch Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 5 Clarification of signs Installation, inspection, commissioning and troubleshooting of the device must only be carried out by a competent electrician. This manual is amended periodically and will be brought into line with new software releases. The change status (software version and date) can be found in the contents footer. If you have a device with a later software version, please check www.elsner-elektronik.de in the menu area "Service"...
  • Page 6 Clarification of signs...
  • Page 7: Description

    (mixed value). The KNX T-L-Pr-UP Touch has a settable brightness limit. The limit output and other communication objects can be connected with an AND and OR logic gate.
  • Page 8: Accuracy Of The Measurement

    ETS in order to ensure the specified accuracy of the sensor (offset). When measuring temperature, the self-heating of the device is considered by the electronics. The heating is compensated by the software. Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 9: Installation And Commissioning

    Elsner Elektronik is not liable for any changes in norms and standards which may occur after publication of these operating instructions.
  • Page 10: Detection Range Of The Presence Sensor

    ETS in order to ensure the specified accuracy of the sensor (offset). 2.2.1. Detection range of the presence sensor Detection range: horizontal approx. 150°, vertical approx. 35° Range: approx. 5 m Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 11: Device Structure

    (seen from the side) 35° Wall 2.3. Device structure 2.3.1. Housing Fig. 4 Front LEDs Presence sensor Touch buttons Ventilation slots (top and bottom) Position of the brightness sensor Breaks Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 12: Installing The Sensor

    Presence and brightness sensor, and the ventilation slots, must not become dirty or be covered. As a rule, it is sufficient to wipe the device with a soft, dry cloth as required. Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 13: Disposal

    Disposal After use, the device must be disposed of or recycled in accordance with the legal reg- ulations. Do not dispose of it with the household waste! Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 14: Transfer Protocol

    Motion sensor: Master 1: Input / RWCT [9.4] DPT_Value_Lux 2 Bytes Brightness threshold value On Output Motion sensor: Master 1: Input / RWCT [9.4] DPT_Value_Lux 2 Bytes Brightness hysteresis Output Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 15 R-CT [1.1] DPT_Switch 1 Bit tion Temperature sensor: Measure- Input -SKÜ [9.1] DPT_Value_Temp 2 Bytes ment, external Temperature sensor: Measure- Output R-CT [9.1] DPT_Value_Temp 2 Bytes ment Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 16 Input -WC- [1.2] DPT_Bool 1 Bit Logic input 8 Input -WC- [1.2] DPT_Bool 1 Bit AND logic 1: 1-bit switching Output R-CT [1.2] DPT_Bool 1 Bit output Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 17 OR logic 2: 8-bit output A Output R-CT 1 Byte OR logic 2: 8-bit output B Output R-CT 1 Byte OR logic 2: Block Input -WC- [1.1] DPT_Switch 1 Bit Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 18: Parameter Setting

    The brightness reading can be corrected in order to compensate for a dull or bright point of installation for the sensor. Use reading correction No • Yes Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 19: Brightness Threshold Value

    Threshold value setpoint using Parameter • Communications object When the threshold value per parameter is specified, then the value is set. Threshold value in kLux 1 … 5000; 200 Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 20: Switching Output

    No • Yes Analysis of the blocking object • At value 1: block | At value 0: release • At value 0: block | At value 1: release Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 21: Motion Detector

    • at value 1: release | at value 0: block • at value 0: release | at value 1: block Value prior to first communication 0 • 1 Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 22 Cycle reset object type • 1 bit • 1 byte (0%...100%) Cycle reset at value 0 • 1 and/or 0...100; 1 Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 23: Master 1/2

    Then specify the switch-on and switch-off values (brightness range). The switch-on value is the value, below which the room should be lit in the event of move- Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 24 Settings for all types of motion detection: The following settings can be made, independent of the motion detection type, i.e. for "constant" and "brightness dependent" motion recognition. Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 25 In addition, you can refer to a slave signal, i.e. a signal from an additional motion de- tector, for controlling purposes. Use slave signal No • Yes Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 26: Align Communication Between Master And Slave

    "slave: cycle reset" in order to immediately send a message to the bus in the event of a motion detection. The master receives the motion message without having to wait for the next slave transmission cycle. Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 27: Temperature Measurement

    "Reset temperature min/max. value" objects to reset the values to the current readings. The values are not retained after a reset. Use minimum and maximum value No • Yes Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 28: Buttons

    Use additional function for button held down Command when pressing the button • Switching • Do not send message Command when releasing the button • Switching • Do not send message Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 29 Time between short and long 0 ... 50; 10 in 0.1 seconds Repeat the step command every 0.1 s • every 2 sec; every 0.5 sec for a long button press Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 30 Stop released after time 1 +2 no more stop Time 1 (in 0,1 s) 0 ... 50; 4 Time 2 (in 0,1 s) 0 ... 50; 20 Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 31 0 ... 50; 4 Time 2 (in 0,1 s) 0 ... 50; 20 Dead man‘s switch: Push button Retract- | Extend- | Retract/Extend com- mand Release button Stop command Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 32 0,1 s • ... • every 0,5 s • ... • every 2 s upon extended button actuation Dimming by 100% • ... • 6% • ... • 1,5% Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 33: Leds

    The device has 8 logic inputs, two AND and two OR logic gates. Activate the logic inputs and assign object values up to first call. Use logic inputs Yes • No Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 34: And Logic

    • Percent (0…100%) • Angle (0…360°) • Scene call-up (0…63) Output value object A 0 … 255 / 100% / 360° / 63; 1 if logic = 1 Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 35: Block

    • Do not send message On block • Transmit block value [see above, Output value if blocking active] On release [send value for current logic status] (with 2 seconds release delay) Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 36: Monitoring

    Motion detector master 1 output Motion detector master 1 output inverted Motion detector master 2 output Motion detector master 2 output inverted Switching output brightness Switching output brightness inverted Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 37 OR logic: Switching output AND logic 1 Switching output AND logic 1 inverted Switching output AND logic 2 Switching output AND logic 2 inverted Sensor KNX T-L-Pr-UP Touch • Version: 17.09.2020 • Technical changes and errors excepted.
  • Page 38 Elsner Elektronik GmbH Control and Automation Engineering Sohlengrund 16 75395 Ostelsheim Phone +49 (0) 70 33 / 30 945-0 info@elsner-elektronik.de Germany +49 (0) 70 33 / 30 945-20 www.elsner-elektronik.de Technical support: +49 (0) 70 33 / 30 945-250...