Wireless Remote Controller (40VM900001) —
Indoor unit addressing can be performed using the wireless
remote controller. When using the wireless controller, the
user must maintain a line of sight with the receiver on the
indoor unit. See Fig. 32 for a description of the buttons on
the wireless remote.
Fig. 32 —Wireless Remote Controller
(40VM900001)
Use a tool to press and hold LOCK for at least ten seconds,
then press
to activate. Click
press to send the setting. To display an indoor unit address, use
the same tool to press and hold LOCK for at least 10 seconds,
and press
to query the address.
or
to select an address and
Programmable Controller — When setting an address,
connect only one wired controller to an indoor unit.
1. Press FAN and BACK simultaneously for five seconds to
access the parameter settings as shown in Fig. 33.
Fig. 33 —Programmable Controller IDU
Addressing Menu
2. Press TEMP. UP or TEMP. DOWN to move cursor, and
select IDU ADDRESSING. Select MENU/OK to access
this setting.
3. Press TEMP. UP or TEMP. DOWN to choose the
address you want to set. See Fig. 34. Press MENU/OK to
send this address to the IDU.
MODE
F
A
N
Fig. 34 —Programmable Controller Setting IDU
4. Press BACK twice or wait 30 seconds to automatically
exit the parameter settings menu.
18
TEMP. UP
ON/OFF
MENU
OK
T
E
M
. P
D
O
W
N
BACK
Address