Carrier 40VMZ Installation And Maintenance Instructions Manual page 14

Reheat unit for variable refrigerant flow (vrf) systems
Table of Contents

Advertisement

outdoor unit
L1
Main MDC unit
L2
MDC unit
MAXIMUM WIRING LENGTH
L1+L2 < 3937 ft 18 AWG, 2-Core Stranded Shield
L3 < 3937 ft 18 AWG, 2-Core Stranded Shield
L4 < 3937 ft 18 AWG, 2-Core Stranded Shield
L5 < 3937 ft 18 AWG, 2-Core Stranded Shield
L6+L7+L8+L9 < 820 ft 18 AWG, 2-Core Stranded Shield
L10+L11 < 820 ft 18 AWG, 2-Core Stranded Shield
Fig. 25 —Typical Heat Recovery System Communication Wiring
Centralized controller
L5
L3
L3
L3
L3
L4
L4
14
wired controller
Indoor unit 1#
L6
Outside Air Unit
wired controller
CN50
CN51
FAN CTON HTON AUXH
ACB interface
L11
CN54
OFF GND
L6
wired controller
Indoor unit 2#
Reheat unit
L6
wired controller
Indoor unit 3#
L6
Indoor unit 4#
wired controller
L10
wired controller
Indoor unit 5#
L10
Indoor unit 6#