M-system R7G4HH-A-YVF4 Instruction Manual page 4

Hi-speed link system i/o module (high-speed dc voltage output, 4 points, isolated, screw terminal block)
Table of Contents

Advertisement

■ NETWORK
Recommended cable connector: TM21P–88LP (Hirose Electric)
(not included in the package)
• Communication connector pin assignment Blank: 3, 4 – 5, 6 pair wiring
  (M-System HLS related device standard pin assignment)
Full-duplex communication
12345678
1. NC
Unused
2. NC
Unused
3. TXD+
Network (slave, transmission +)
4. TXD–
Network (slave, transmission –)
5. RXD+
Network (master, transmission +)
6. RXD–
Network (master, transmission –)
7. NC
Unused
8. SLD
Shield
• Communication connector pin assignment /E: 4, 5 – 3, 6 pair wiring (Ethernet cable pin assignment)
Full-duplex communication
12345678
1. NC
Unused
2. NC
Unused
3. TXD+
Network (slave, transmission +)
4. RXD–
Network (master, transmission –)
5. RXD+
Network (master, transmission +)
6. TXD–
Network (slave, transmission –)
7. NC
Unused
8. SLD
Shield
PC CONFIGURATOR
The following parameter items can be set with using PC Configurator Software (model: R7CFG).
Refer to the users manual for the R7CFG for detailed operation of the software program.
■ CHANNEL INDIVIDUAL SETTING
PARAMETER
SETTING RANGE
Validating/
Valid
Invalidating
Invalid
Output range
-10 to +10V DC
-5 to +5V DC
-1 to +1V DC
0 to 10V DC
0 to 5V DC
1 to 5V DC
0 to 1V DC
-0.5 to +0.5V DC
Bias
-320.00 to +320.00 (%) 0.00 (%)
Gain
-3.2000 to +3.2000
Zero scale
-32000 to +32000
Full scale
-32000 to +32000
Output clear
-15.00 to +115.00 (%) -15.00 (%)
value*
1
Half-duplex communication
Half-duplex communication
DEFAULT
SETTING
Valid
-10 to +10V DC
1.0000
0
10000
5-2-55, Minamitsumori, Nishinari-ku, Osaka 557-0063 JAPAN
Phone: +81(6)6659-8201 Fax: +81(6)6659-8510 E-mail: info@m-system.co.jp
12345678
1. NC
Unused
2. NC
Unused
3. TR+
Network (+)
4. TR–
Network (–)
5. NC
Unused
6. NC
Unused
7. NC
Unused
8. SLD
Shield
12345678
1. NC
Unused
2. NC
Unused
3. NC
Unused
4. TR–
Network (–)
5. TR+
Network (+)
6. NC
Unused
7. NC
Unused
8. SLD
Shield
■ CHANNEL BATCH SETTING
PARAMETER
SETTING RANGE
Setting output at
Hold
the loss of commu-
Clear
nication
*1. When output range is -10 to +10V DC, approx. -11.5V DC
at approx. -7.5 to -15% and approx. 11.5V DC at approx.
107.5 to 115% are outputted respectively.
R7G4HH-A-YVF4
DEFAULT
SETTING
Hold
EM-7777-F Rev.2 P. 4 / 9

Advertisement

Table of Contents
loading