Download Print this page

Siemens SICAM SGU 7XV5676 Manual page 9

Advertisement

Available languages

Available languages

s
Repair
CAUTION
Danger of damage due to static electrical charges
The user is not authorized to repair the device when it is defective. This
is because the device contains special electronic components that may
only be handled by the manufacturer in compliance with the regulations
for electrostatic sensitive devices (ESD).
Furthermore, hazardous voltages can lead to lethal injuries when the
work is performed improperly.
If you suspect that the device has a defect, Siemens recommends to
send the entire device back to the manufacturer.
Cleaning
Switch off the device. Wiped the device with a clean, dry and soft cloth. Do not use
solvents.
Repacking a Device
If you store devices after incoming inspection, pack them in suitable storage pack-
aging.
If devices are to be transported, pack them in transport packing.
Put the accessories supplied and the test certificate in the packing with the device.
Storage
Only store devices on which you have carried out an incoming inspection, thus
ensuring that the warranty remains valid.
Store the device in a dry and clean location.
The relative air humidity must not lead to condensation or ice formation.
To avoid premature aging of the electrolytic capacitors, store the device within the
recommended temperature range of +10 °C to +35 °C (+50 °F to +95 °F).
If the device is stored for an extended period of time, Siemens recommend to
connect the device to the supply voltage for 1 or 2 days once a year to reform the
electrolytic capacitors in the device. This procedure should also be carried out be-
fore operating the device.
Transport
For reshipment, Siemens recommends using the original transport packaging of the
devices. If you use another packaging, make sure that the packaging meets the re-
quirements concerning the stress during transport according to the requirements of
standard ISO 2248. The storage packing of the individual devices is not adequate
for transport purposes.
The Lithium-batteries in our equipment are subject to Special Provision 188 of the
UN Recommendations on the Transport of Dangerous Goods Model Regulations
and Special Provision A45 of the IATA Dangerous Goods Regulation and the ICAO
Technical Instructions. This is only valid for the original battery or original spare bat-
teries.
Technical Data
SICAM SGU 7XV5676-0JJ00-7AA1 (Terminal Block H)
Supply Voltage – Direct Voltage
Rated input voltages
Admissible input voltage tolerance
Permitted ripple of the input voltage
Maximum inrush current at ≤ 110 V
Maximum inrush current at 220 V to 300 V
Supply Voltage – Alternating Voltage
Rated input voltages
System frequency
Admissible input voltage tolerance
Permitted harmonics
Maximum inrush current at ≤ 115 V
Maximum inrush current at 230 V
Internal fuse, not replaceable
Internal fuse, secondary, not replaceable
Product Information
E50417-B1050-C554-A4, Edition 03.2015
DC 24 V to 250 V
±20 %
15 %
< 15 A
≤ 22 A; after 250 µs: < 5 A
AC 110 V to 230 V
50 Hz/60 Hz
±20 %
2 kHz
< 15 A
≤ 22 A; after 250 µs: < 5 A
Fuses
T1.6A/250V acc. to IEC 60127
F2A/125V acc. to UL 248-14
SICAM SGU 7XV5676-xJx70-8AA2 (Terminal Block X)
Rated input voltages
Admissible input voltage tolerance
Maximum input current
Permitted ripple of the input voltage
Power input
Internal fuse, not replaceable
Environmental Conditions (for indoor operation only)
Temperature Data
Operating temperature
Temperature during transport and storage
Air humidity data
Mean relative humidity per year
Maximum relative humidity
Condensation during operation
Condensation during transport and storage
Other environmental data
Max. altitude above sea level
Degree of pollution
GSM Antenna and Antenna Interface
Requirements for Antenna Type
Fixed antenna
Detached antenna
Antenna gain
GSM 1900
GSM 850
Connection values
Impedance
VSWR
Antenna Interface at the Device
Type of antenna socket
Communication Mobile
GSM frequency bands
Maximum data rate
General data
SICAM SGU Devices
DC 24 V SELV
DC 19 V to 28.8 V
1 A
±15 %
6.1 W: 7XV5676-xJJ70-8AA2
7.8 W: 7XV5676-xJL70-8AA2
Fuse
2 A, slow-blow
-10 °C to +55 °C
(+14 °F to 131 °F)
-25 °C to +70 °C
(-13 °F to +158 °F)
≤ 75 %
95 % 30 days a year
Not permitted
Permitted
2000 m
2
For use in industrial environment acc.
to IEC 61010-1 Ed. 3 CAT III
For remote installation in residential,
commercial and light industrial
environments
(IEC 61010-1 Ed. 3 CAT III).
Antenna Data
≤ 8.4 dBi
≤ 2.9 dBi
Approx. 50 Ohm
1:2.5 or better
SMA
850 MHz
900 MHz
1800 MHz
1900 MHz
Up to 80 kbps uplink
Up to 40 kbps downlink
GPRS multislot class 10,
Coding schema CS 1-4
7XV5676