Download Print this page

Siemens SICAM SGU 7XV5676 Manual page 8

Advertisement

Available languages

Available languages

SICAM SGU Devices
7XV5676
NOTE
The snap-on clip is adjusted to a certain height setting by the manufac-
turer. You can change this position if necessary. To do so, lever the
release device out of its guiding (no special tool required) and move
the release device into the desired position. Subsequently, press the
release device back into its guiding.
Communication Mobile
Danger
Risk of lightning strikes when installed outdoors
Non-observance leads to death or serious injury.
If you install an antenna outside, the antenna must be grounded to
protect it from lightning strikes. This work must only be carried out by
qualified personnel. Antennas installed outdoors must be within the
area covered by a lightning protection system. Make sure that all
conducting systems entering from outdoors can be protected by a
lightning protection potential equalization system. When implementing
your lightning protection concept, make sure you adhere to the VDE
0182 or IEC 62305 standard.
Commissioning
Check that the operational data match the rated data on the label and the technical
data of the device. This applies in particular to the supply voltage and to the maxi-
mum values.
Connect the desired devices to the terminals and plug connectors (see figures 1 to
3).
Install the SIM card and connect the GSM antenna according to Device Manual
(only 7XV5676-xJx70-8AA2).
Switch on the connected peripheral devices and the supply voltage of the device.
NOTE
The device does not have a power on/off switch. Switch on/off the
supply voltage at the respective isolating device.
The cable length between SICAM SGU and the external power supply
must not exceed 0.5 m.
NOTE
Use copper conductors only.
NOTE
Field wires of control circuits shall be separated from other circuits with
respect to the end use requirements.
Operation
Prerequisites
Most control functions require the input of passwords. This applies to all entries affecting
the device functions.
No password is required to read out data, indications, and diagnostic data.
NOTE
The device comes delivered with the following default passwords:
- Activation password: 000000
- Maintenance password: 311299
Once commissioning has been completed, you should change the passwords to protect
the device against unintentional changes and operation by unauthorized persons. How to
change the passwords is described in the device manual.
The devices are operated via the connected PC using WebBrowser.
Operation is described in detail in the respective device manual. In the following, the most
important settings are described:
8
The graphical user interface is stored in the device. To display the user interface, start
Microsoft Internet Explorer 8.0 (or higher) and enter the IP address (default IP address:
192.168.0.55; also see label on the side of the device) of the device.
You can navigate through browser (for example Microsoft Internet Explorer) using the
icons on the toolbar, for example back, forward, print etc. The user interface itself does
not contain any navigation icons.
The following table lists the control elements:
Control Element
Structure of the HTML pages
NOTE (for 7XV5676-xJx70-8AA2 only)
Request in accordance with EN 301511:
The Ethernet port must be switched off after putting into operation and
as long as the Ethernet interface is not needed over the button "IP
Addr". The communication then takes place only about mobile commu-
nication.
s
Control Function
Option button: selects one option
List box: selects an item from a list
Button: Executing an action by clicking
the button, that is the current settings on
the user interface are transmitted to the
device.
Active tab (light blue)
Inactive tab (dark blue)
Selects and opens the item to be acti-
vated, for example a tab
Product Information
E50417-B1050-C554-A4, Edition 03.2015

Advertisement

loading