Hitachi MICRO-EHV+ Applications Manual page 159

Table of Contents

Advertisement

(5) Input wiring for the input terminal
Item
Current-output-type
proximity switch
24V
(a) DC input
1] When each input and common terminal (C) are loaded with 24VDC, the input status changes to ON, and
approximately 4.8mA or 8 mA (depending on input numbers) current flow to the external input contacts.
2] For sensors such as a proximity switch and photoelectric switch, current-output-type (transistor open
collector) can be directly connected. For voltage-output-type sensors, connect them to the input terminal
after first going through the transistor.
3] Measures to prevent faulty contact in a strong electric contact
Strong electric
contact
Approx.
50mA
24V DC
4] Limit the wiring length within 30 m (98.43ft.).
5] Each common on the input terminal block is independent of each other. Make an external connection as
needed.
DC input
0V
[1]
[3]
[5]
[0]
[2]
[4]
[6]
NPN open collector type encoder
1
24V
3
0V
0
2
4
PNP open collector type encoder
NPN voltage output type encoder
1
24V
3
0V
0
2
4
Figure 4.5 Input wiring
0
+
3 W
560 
C
Rotary encoder
24V DC
0V
[C0]
24V
A
B
Z
24V
0V
5
15
14
C0
A
B
Z
24V
0V
5
15
14
C0
The current that flows to a contact when external contacts
are closed is approximately 4.8mA or 8mA. If the use of a
strong electric contact cannot be avoided, add resistance as
shown in the diagram at left and supply sufficient current to
the contact to prevent a faulty contact.
4 – 5
Chapter 4
DC input (High speed counter)
24V DC
1kΩ, 3W
[1]
[3]
[0]
[2]
Installation
[C0]