Power Supply For Sensors - Hitachi MICRO-EHV+ Applications Manual

Table of Contents

Advertisement

■ Pulse train output / PWM output specifications
Output
Load voltage
PWM highest output frequency *
Pulse train highest output frequency *
*: Though Pulse train output and PWM output are available for relay output type, it is not recommended to use because
relay outputs cannot react high frequency.
2.8

Power supply for sensors

24V terminal on the input terminal block can supply current to the external equipments. If this output is used as the
power supply for the input of own unit, the remaining can be used as power supply for the sensors. The current (I)
allowed using as the power supply for sensors can be calculated by the following formula.
I = 430 mA – (5 mA* × NI + 5mA × NO)
NI: number of input in active at the same time
NO: number of output in active at the same time
*: Replace 10mA instead of 5mA for input bit 0, 2, 4, 6 and 8.
Item
64-point / 40-point / 20-point transistor output
0 to 2 (configurable)
12 / 24 V
65,535Hz
65,535Hz
2 – 11
Chapter 2
Specifications