Power supply connections
If the air handler has been installed prior to installing the electric heaters or if an older unit is being replaced, the supply
power wires must be checked to make sure the wires are the proper sizes to handle the current load for the heaters. Refer
to table below for correct wire size. If the supply power wire size is incorrect, new wires will need to be installed. Follow the
instructions "Power Supply Wiring" on page 18 of these instructions for proper installation.
Electric Heater Data
Indoor Unit
Amps
Model
208V
Circuit
Kw (2)
Qty.
Circuit
1
0
AM012TNZDCH
1
3
10.90
0
0
AM018TNZDCH
1
3
10.90
AM024TNZDCH
1
5
18.03
1
0
AM030TNZDCH
1
5
18.03
AM036TNZDCH
1
10
36.06
1
0
AM048TNZDCH
1
5
18.0
1
10
1
0
AM054TNZDCH
1
5
18.0
AM060TNZDCH
1
10
2
15
18.0
1
0
1
5
18.0
AM072TNZDCH
1
10
2
15
18.0
2
20
1. Rated Motor Amps (at DOE External Static Rating Point)
2. Nominal Kw At 240V (Derate 25% For 208V)
3. Fuse or HACR Breaker
4. Maximum Overcurrent Device, Overcurrent Protection Installed On Breaker Models Are Sized Per MCA
• To prevent damage, carefully insert the electric heating assembly through the rectangular opening in the front of the
discharge opening so the heat element support rod is seated into the hole on the back side of the discharge opening.
• After installing the electric heater, a one inch clearance must be maintained on all sides of the supply air duct and/or
plenum for a minimum of thirty six inches from the air handler discharge opening.
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 23
ELECTRICAL DATA
Minimum Circuit
Ampacity (MCA)
Amps
Amps
Amps
208V 208V 240V 240V
208V
240V
240V
Circuit
Circuit
Circuit
Circuit
Circuit
Circuit
1
2
1
2
1
2
SMALL CABINET-NOMINAL1.0, 1.5 & 2.0 TONS (0 To 5 Kw)
0
-
0
-
0.90
-
0.90
-
12.50
-
13.63
-
15.63
0
-
0
-
0.90
-
0.90
-
12.50
-
13.63
-
15.63
-
20.83
-
23.26
-
26.76
MEDIUM CABINET-NOMINAL 2.5, 3.0 TONS (0 To 10 Kw)
-
-
2.08
-
2.08
-
20.83
-
24.20
-
27.70
-
41.67
-
46.73
-
53.74
LARGE CABINET-NOMINAL 4.0, 4.5, 5.0, 6.0 TONS (0 To 20 Kw)
-
-
2
-
-
20.8
-
24.6
-
26.0
36.1
-
41.7
-
45.1
-
52.1
-
-
2
-
-
20.8
-
24.6
-
26.0
36.1
-
41.7
-
45.1
-
52.1
36.1
20.8
41.7
24.6
47.2
28.1
-
-
7
-
-
20.8
-
28.3
-
26.0
36.1
-
41.7
-
45.1
-
52.1
36.1
20.8
41.7
28.2
50.8
31.7
36.1
36.1
41.7
41.7
50.8
50.8
57.8
Maximum Overcurrent
Protection (MOCP)
208V
208V
240V
240V
(3,4)
(3,4)
(3,4)
(3,4)
75°C /
Circuit
Circuit
Circuit
Circuit
Circuit
90°C
1
2
1
2
1
2
-
10.0
-
10.0
-
#14
-
15.0
-
20.0
-
#12
-
10.0
-
10.0
-
#14
-
15.0
-
20.0
-
#12
-
30.0
-
30.0
-
#10
-
10.0
-
10.0
-
#14
-
30.0
-
30.0
-
#10
-
50.0
-
60.0
-
#6
2.6
-
15.06
-
15.0
-
#14
-
30.0
-
30.0
-
#10
-
50.0
-
60.0
-
#6
2.6
-
15.06
-
15.0
-
#14
-
30.0
-
30.0
-
#10
-
50.0
-
60.0
-
#6
54.2
30.0
50.0
30.0
60.0
#6
7.2
-
15.02
-
15.0
-
#14
-
30.0
-
30.0
-
#10
-
50.0
-
60.0
-
#6
57.8
30.0
60.0
35.0
60.0
#6
57.8
60.0
60.0
60.0
60.0
#6
Minimum Wire Size
Short-Circuit
(AWG)
Current Rating
Circuit 1
Circuit 2
"SCCR"
75°C /
kA rms
V
60°C
60°C
90°C
symmetrical
maximum
#14
-
-
n/a
n/a
#12
-
-
n/a
n/a
#14
-
-
n/a
n/a
#12
-
-
n/a
n/a
#10
-
-
n/a
n/a
#14
-
-
n/a
n/a
#10
-
-
n/a
n/a
#4
-
-
n/a
n/a
#14
-
-
n/a
n/a
#10
-
-
n/a
n/a
#4
-
-
n/a
n/a
#14
-
-
n/a
n/a
#10
-
-
n/a
n/a
#4
-
-
n/a
n/a
#4
#10
#10
5
240
#14
-
-
n/a
n/a
#10
-
-
n/a
n/a
#4
-
-
n/a
n/a
#4
#10
#10
5
240
#4
#6
#4
5
240
English