Performing leak test & insulation
5. Select the insulation of the refrigerant pipe.
• Insulate the gas side and liquid side pipe referring to the thickness according to the pipe size.
• Indoor temperature of 86 °F(30 °C) and humidity of 85% is the standard condition. If install in a high humidity
condition,use one grade thicker insulator by referring to the table below. If installing in an unfavorable conditions,
use a thicker wall insulation.
• Insulator's heat-resistance temperature should be more than 248 °F (120 °C).
Pipe
6.35~9.52
Liquid pipe
12.7~50.8
9.52~25.4
Gas pipe
28.58~44.45
• When installing insulation in places and conditions below, use the same insulation that is used for high humidity
conditions.
<Geological condition>
‐ High humidity places such as shoreline, hot spring, near lake or river, and ridge (when the part of the building is
covered by earth and sand.)
<Operation purpose condition>
‐ Restaurant ceiling, sauna, swimming pool etc.
<Building construction condition>
‐ The ceiling frequently exposed to moisture and cooling is not covered.
e.g. The pipe installed at a corridor of a dormitory and studio or near an exit that opens and closes frequently.
‐ The place where the pipe is installed is highly humid due to the lack of ventilation system.
16 English
AM072TNZDCH_IM_DVM V-AHU_AA_EN_.indd 16
General [30°C (86°F),
Outer diameter
mm
inch
mm
1/4~3/8
1/2~2
13
6.35
1/4
13
3/8~1
19
1 1/8~1 3/4
19
50.8
2
25
Insulation Type (Cooling/Heating)
High humidity [30°C
85% or below]
(86°F), more than 85%]
EPDM, NBR
inch
mm
9
3/8
9
1/2
13
1/2
19
3/4
25
3/4
32
1
38
Remarks
inch
3/8
1/2
Internal
temperature
3/4
is higher
1
than 248 °F
(120 °C)
1 1/4
1 1/2
2020-02-14 오전 10:33:32