Hitachi S10mini Hardware Manual page 39

Option j.net
Hide thumbs Also See for S10mini:
Table of Contents

Advertisement

4 USER GUIDE
Basic form of arithmetic function:
○○○○: Arithmetic function name (JCMD, JRSP, JSND, JRCV)
□□□□: First parameter (starting address of send or receive area)
△△△△: Second parameter (number of send/receive area bytes)
Enter a symbol (e.g., FW000) as the first parameter.
Set the starting address of the send or receive area.
Numeric data (e.g., extended memory address) cannot be entered directly.
Set the data length (number of bytes) of the send/receive area.
The second parameter setting range depends on the arithmetic function to be used.
JCMD
4 to 254 bytes
JRSP
4 to 254 bytes
JSND
4 to 516 bytes
JRCV
4 to 516 bytes
Send/receive area
15
8
7
2
—– 2
2
—– 2
0 MDL
SID
2 NET
SVC
4 Data 1
Data 2
6 Data 3
Data N
For the WRITE or READ command, the send/receive area is configured as shown on the next page
because data in the area further requires detailed setting.
0
MDL: Module No. (= 0 for main module; = 1 for sub-module)
SID: Station ID (/01 to /1F)
NET: Net No. (= 0 for N1; = 1 for N2)
SVC: Service code
SVC
/31
/32
/33
Data 1 to data N: 1 to 250 (JCMD, JRSP)
○○○○
#L
Service name
Reset service
Data write service
Broadcast service
1 to 512 (JSND, JRCV)
4-12
: △△△△
□□□□
First
Second
parameter
parameter