Technical Reference Manual, General
'HVLJQ GHVFULSWLRQ
7HFKQLFDO GDWD
7DEOH 
(QHUJL]LQJ LQSXWV
Rated frequency
Current inputs
Voltage inputs
Sensor inputs
7DEOH 
$X[LOLDU\ SRZHU VXSSOLHV
Type
Input voltage, ac
Input voltage, dc
Voltage variation
Burden
Ripple in dc auxiliary voltage
Interruption time in auxiliary dc
voltage without resetting
Internal overtemperature
indication
7DEOH 
'LJLWDO LQSXWV
Type
Operating range, dc
Input voltage, dc
Current drain
Power consumption/input
7DEOH 
6LJQDO RXWSXWV
Max. system voltage
Continuous carry
Make and carry for 0.5 s
Make and carry for 3 s
Breaking capacity when control
circuit time-constant L/R <40 ms,
at 48/110/220 V dc
50.0/60.0 Hz
Rated current
Thermal withstand
continuously
capability
for 1 s
dynamic current withstand, half-wave
value
input impedance
rated voltage
voltage withstand, continuous
burden at rated voltage
voltage range RMS
voltage range peak
input impedance
input capacitance
PS_87H
(REX521xxHxx)
110/120/220/240 V
110/125/220 V
ac 85...110%, dc 80...120% of rated
value
<20 W
max. 12% of the dc value
<40 ms, 110 V
<100 ms, 200 V
+78°C (+75...+83°C)
PS_87H
(REX521xxHxx)
80...265 V dc
DI9: 18...265 V
DI1...DI8: 110/125/220 V
DI9: 24/48/60/110/125/220 V)
~2...25 mA
<0.8 W
250 V ac/dc
5 A
10 A
8 A
1 A/0.25 A/0.15 A
5(; 
0,2 A/1 A/5 A
1.5 A/4 A/20 A
20 A/100 A/500 A
50 A/250 A/1250 A
<750 mΩ/<100mΩ/
<20 mΩ
100 V/110 V/115 V/120 V
(parametrization)
2 x U
(240 V)
n
<0.5 VA
9.4 V RMS
± 12 V
>4.7 MΩ
<1 nF
PS_87L
(REX521xxLxx)
-
24/48/60 V
dc 80...120% of rated value
<15 ms, 24 V
<50 ms, 48 V
PS_87L
(REX521xxLxx)
18...265 V
DI1...DI9:
24/48/60/110/125/220 V