1MRS 751108-MUM
3URWHFWLRQ 5HOD\
Technical Reference Manual, General
9DOXHV WR EH VHW IRU D FXUUHQW VHQVRU 5RJRZVNL FRLO 
• secondary rated voltage of the current sensor used at the preset primary rated
current (100...300 mV)
• primary rated current of the current sensor used (1...6000 A)
• amplitude correction factor of the current sensor used at rated current
(0.9000...1.1000)
• correction parameter for the phase displacement error of the current sensor
(-1.0000°...1.0000°)
9DOXHV WR EH VHW IRU D YROWDJH GLYLGHU
• division ratio of the voltage divider primary and secondary voltage (100...20000)
• rated value of primary phase-to-phase voltage (0.100...440.000 kV)
• amplitude correction factor of the voltage divider (0.9000...1.1000)
• correction parameter for the phase displacement error of the voltage divider
(-1.0000°...1.0000°)
&DOFXODWLRQ RI FRUUHFWLRQ SDUDPHWHUV DQG IDFWRUV
The measurement values stated by the manufacturer of the measuring device are
used for calculating the correction parameters and factors according to the following
formulas:
&XUUHQW WUDQVIRUPHUV
Amplitude error at current I
(p = error in per cent)
Amplitude error at current 0.01 x I
(p = error in per cent)
Phase displacement error at current I
(d = error in degrees)
Phase displacement error at current 0.01 x I
(d = error in degrees)
9ROWDJH WUDQVIRUPHUV
Amplitude error at voltage U
(p = error in per cent)
Phase displacement error at voltage U
(d = error in degrees)
5RJRZVNL FRLO
Amplitude error at the whole measuring range
(e = error in per cent)
Phase displacement error at the whole
measuring range
(e = error in degrees)
Amplitude correction factor 1
n
= 1 / (1+ p/100)
Amplitude correction factor 2
n
= 1 / (1+ p/100)
Phase displacement error 1 = - d
n
Phase displacement error 2 = - d
n
Amplitude correction factor
n
= 1 / (1+ p/100)
Phase displacement error = - d
n
Amplitude correction factor
= 1/(1+ e/100)
Phase displacement error = - e
5(; 
17