ABB Industrial IT enabled REX 521 Technical Reference Manual, General page 15

Protection relay
Hide thumbs Also See for Industrial IT enabled REX 521:

Advertisement

1MRS 751108-MUM



3URWHFWLRQ 5HOD\
Technical Reference Manual, General
2YHUWHPSHUDWXUH LQGLFDWLRQ
The REX protection relay includes an internal temperature supervision function.
The CPU module issues an internal alarm signal when overtemperature has been
detected inside the relay enclosure. The alarm signal will be activated once the
temperature inside the relay enclosure increases approximately to +78
overtemperature indication can be seen on the HMI or as an event via serial
communication. The relay will go to the IRF (internal relay fault) state. See
Table 4.1.11.2-1, "Fault indications," on page 25.
$QDORJXH FKDQQHOV
The protection relay measures the analogue signals needed for protection,
measuring, etc. via galvanically separated matching transformers. In addition,
current sensors (Rogowski coil) and voltage dividers developed by ABB can be used
with REX 521.
The different versions of REX 521 are provided with the following matching
transformers and sensor inputs:
9HUVLRQ
0DWFKLQJ WUDQVIRUPHUV
Basic
CT1, CT2, CT3, CT4
Medium
CT1, CT2, CT3, CT4, CT5, VT1
High
CT1, CT2, CT3, CT4, CT5, VT1, VT2, VT3, VT4 -
Sensor
CT4, CT5, VT1
A letter in the order number specifies whether the protection relay is equipped with
basic, medium, high or sensor measuring input modules. (Refer to section "Ordering
information" on page 48).
6FDOLQJ WKH UDWHG YDOXHV RI WKH SURWHFWHG XQLW IRU DQDORJXH
FKDQQHOV
A separate scaling factor can be set for each analogue channel. The factors enable
differences between the ratings of the protected unit and those of the measuring
device (CTs, VTs etc.) The setting value 1.00 means that the rated value of the
protected unit is exactly the same as that of the measuring device.
When scaling factors are used, it should be noted that they affect the
!
operation accuracy of the relay. The accuracies stated in the description of
each function block (in the CD-ROM
only apply with the default values of the scaling factors. For example, a high
factor affects the operation of sensitive protection functions such as the
directional earth fault protection. To ensure the proper operation of the
function blocks, it must be checked that the analogue scales (pu scales) of
the phase currents I
of the phase-to-phase voltages U
U
, U
, and U
are identical.
1
2
3
7HFKQLFDO 'HVFULSWLRQV RI )XQFWLRQV
, I
, and I
, and correspondingly, the analogue scales
L1
L2
L3
, U
, and U
12
23
5(; 
o
C. The
6HQVRU LQSXWV
-
-
RS1, RS2, RS3, VD1, VD2, VD3
or phase-to-earth voltages
31
)
15