3URWHFWLRQ 5HOD\
Technical Reference Manual, General
HSPO1
)LJ  +LJKVSHHG VLQJOHSROH SRZHU RXWSXW +632
6LQJOHSROH SRZHU RXWSXWV 32
The single-pole power outputs PO1...3 are outputs where the object to be controlled
is connected in series with two heavy-duty output relay contacts, see the Figure
4.1.8.2.-1 below. These outputs can be used for tripping purposes and for circuit
breaker and disconnector control. Two singe-pole outputs may be used to obtain
another double-pole output.
PO1...3
)LJ  6LQJOHSROH SRZHU RXWSXWV 32
6LJQDOOLQJ RXWSXWV 62
The signalling relay outputs (SO1 and SO2) are not heavy-duty outputs and thus
they cannot be used for controlling, for example, a circuit breaker. Available relay
contacts are Normally Open/Normally Closed type (NO/NC), see the Figure
4.1.8.3.-1 below. These outputs can be used for alarming and other signalling
purposes.
NO/NC
e.g.
SO1
)LJ  6LJQDOOLQJ RXWSXW 62
+
CB
-
+
CB
-
1MRS 751108-MUM
doubpolerex
PO1connrex
NoncRex