NOTE: Use dehumidification chart in section 29 to properly
setup dehumidification based on thermostat selected.

20 Auxiliary Alarm Switch

The control is equipped with a 24VAC Aux Alarm to be used
for a condensate switch install (designated by CONDEN-
SATE IN/OUT on the control). By default, the connected
AUX switch is normally closed and opens when the water
level in the evaporator coil base pan reaches an undesir-
able level. The control responds by displaying a "EDF" er-
ror code and turning off the outdoor condensing unit. If the
AUX switch is detected to be in the closed position for 30
seconds, normal operation resumes and the error message
is no longer displayed. See Figure 19 for the connection
location.

21 Push Buttons

FIGURE 18
The air handler includes three on-board push buttons al-
lowing users to navigate indoor and outdoor system menus.
The Right and Left buttons allow the user to scroll through
the main menus and to then scroll through available options
within specific menus. The Center button is used to enter
into a main menu and to then permanently select options
within those menus.
NOTE: After scrolling to the desired option within a menu,
that option may be flashing on the 7-segment displays. This
indicates the option has not been officially selected. Press-
ing the Center button two times will select that option. The
first press will stop the flashing. The second will make the
selection official and return you to the main menu.
15