The heating mode temperature rise is dependent upon the
system airflow, the supply voltage, and the heat kit size (kW)
selected. Use data provided in Tables 4, 5 and 6 to deter-
mine the temperature rise (°F).
For installations not indicated above the following formula is
to be used:
TR = (kW x 3412) x (Voltage Correction) / (1.08 x CFM)
Where:
TR
kW
3412
VC*
1.08
CFM
*VC (Voltage Correction)
HEAT KIT NOMINAL KW
CFM
3
5
6
800
12
19
24
1000
9
15
19
1200
8
13
16
1400
7
11
14
1600
6
9
12
1800
5
8
11
2000
5
8
9
240/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
HEAT KIT NOMINAL KW
CFM
3
5
6
800
11
18
23
1000
9
15
18
1200
8
12
15
1400
6
10
13
1600
6
9
11
1800
5
8
10
2000
5
7
9
230/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
= Temperature Rise
= Heater Kit Actual kW
= Btu per kW
= .96 (230 Supply Volts)
= .92 (220 Supply Volts)
= .87 (208 Supply Volts)
= Constant
= Measured Airflow
8
10
15
32
38
25
30
45
21
25
38
18
22
32
16
19
28
14
17
25
13
15
23
TABLE 4
8
10
15
30
36
24
29
44
20
24
36
17
21
31
15
18
27
13
16
24
12
15
22
TABLE 5
CFM
3
800
10
1000
8
1200
7
1400
6
1600
5
1800
5
2000
4
208/1/60 SUPPLY VOLTAGE - TEMP. RISE °F
Model
AVPEC25B14 550
AVPEC37C14 850
20
25
AVPEC59D14 990
AVPEC61D14 1030 1030 1150 1250 1320 1650
51
63
43
54
Heat Kit Selection
38
47
34
42
For heat kit selection, see the Specification Sheet for each
30
38
specific Air Handler.

12 Electrical and Control Wiring

IMPORTANT: All routing of electrical wiring must be made
through provided electrical knockouts. When removing the
20
25
electrical knockouts, take care not to damage the PCB. Do
not cut, puncture or alter the cabinet for electrical wiring.
49
61
42
52
FIRE HAZARD!
36
45
To avoid the risk of property damage, personal injury or fire, use
32
40
only copper conductors.
29
36
HIGH VOLTAGE!
Disconnect ALL power before servicing. Multiple
power sources may be present. Failure to do so
may cause property damage, personal injury or
death.
10
HEAT KIT NOMINAL KW
5
6
8
10
16
21
27
33
13
16
22
26
11
14
18
22
9
12
16
19
8
10
14
16
7
9
12
15
7
8
11
13
TABLE 6
Heater (kW)
3
5
6
8
10
650
700
715
875
850
900
100 1120 1220 1250
990 1110 1200 1240 1520
MINIMUM CFM REQUIRED FOR HEATER KITS
TABLE 7
CAUTION
WARNING
15
20
25
40
33
44
55
28
38
47
25
33
41
22
29
37
20
26
33
15
19
20
25
1520
1690 1715