AM-5150
Ambient Air Monitor
Manual
Manual part number
80003-550
MCN-453, 07/19/11

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the AM-5150 and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for ENMET AM-5150

  • Page 1 ENMET Corporation PO Box 979 Ann Arbor, MI 48106-0979 www.enmet.com AM-5150 Ambient Air Monitor Manual Manual part number 80003-550 MCN-453, 07/19/11...
  • Page 2: Table Of Contents

    1.1 U ....................................1 NPACK 1.2 C ..................................1 HECK RDER 1.3 S ................................1 ERIAL UMBERS 2.0 COMPONENTS OF THE AM-5150 ..........................2 2.1 AM-5150 ................................2 ELEMENTS 2.2 AM-5150 O ........................... 2 PERATIONAL EATURES 2.3 C ..............................3 IRCUIT...
  • Page 3: Introduction

    1.2 Check Order Check, the contents of the shipment against the purchase order. Verify that the AM-5150 is received as ordered. Each AM- 5150 is labeled with its target gas. If there are accessories on the order, ascertain that they are present. Check the contents of calibration kits.
  • Page 4: Components Of The Am-5150

    See Section 4.0 and 5.0 for operational and maintenance flow charts. Three alarm points are preprogrammed into the AM-5150. At each alarm point, an LED on the front panel is activated. There are 4, 10 Amp relay contacts at each alarm point, plus a fault relay. See Section 3.2 for wiring information.
  • Page 5: Circuit Board Features

    Sensor connection, See Section 3.2 Data Terminal J19 RS-485 input/output Potentiometer 4 Sensor heater voltage adjustment, See Section 3.2.1 Potentiometer 2 & 3 Not used in AM-5150 Do Not Adjust RS-485 Input/Output Terminal J19 POT 2 Relay Terminals J14, J15, J16, J17...
  • Page 6: Installation Of The Am-5150

    ENMET Corporation 3.0 Installation of the AM-5150 The AM-5150 is supplied with a strain relief for a power line cord. Use this fitting or connect a conduit fitting when supplying power to the unit. : This control panel is N rated for hazardous locations.
  • Page 7: Sensor Location

    If you have a question involving the location of a unit or sensor, please contact your distributor or ENMET personnel. A technician will analyze the question and recommend a location.
  • Page 8: Sensor Hook-Up

    Wire length between the AM-5150 and the sensor greater then 100ft will require that the sensor heater voltage be reset. After you mount and install the AM-5150 and Sensor, you must verify the sensor heater voltage. Use position 2 and 3 to measure heater voltage.
  • Page 9: Relay Contacts

    It is recommended that power for auxiliary equipment be supplied from an independent power source separate form the AM-5150. Use the existing hole in the enclosure for wire to enter and exit and use appropriate cable fittings. Wiring should be grouped together, V wires should be separated for V wires.
  • Page 10: Operation

    4.0 Operation When the AM-5150 is installed as described in Section 3, and in clean air, the POWER green LED is on, the display is lit and the information on the display is measurement of the target detected by the AM-5150. The red alarm and fault LEDs are not lit.
  • Page 11: Normal Display Mode

    4.2 Normal Display Mode When the AM-5150 is installed as described in section 3, and in clean air, the POWER green LED is on, the display is lit and the information on the display in measurement units of ppm or %LEL detected by the AM-5150. The red alarm and fault LEDs are not lit.
  • Page 12: Maintenance

    Press and hold the M button for 2 – 4 seconds to enter the Maintenance Menu The Power/Fault LED will flash Green – Red to indicate the AM-5150 is in Maintenance Mode To exit the maintenance Menu and return to the...
  • Page 13 Press the S button to initiate Zero adjustment ELECT If the Zero signal is within Preset Specs the AM-5150 will display Cal OK, See Section 5.2.2 If the Zero signal is not within Preset Specs the AM-5150 will Bad ZERO...
  • Page 14: Calibration Of The Am-5150

    Span function sets the sensitivity of the instrument. Initial Calibration: Wait at least 3 – 4 hours after initially supplying power to the AM-5150 instrument before initial calibration, overnight is preferred. The AM-5150 has been pre-calibrated at the factory, and initial field calibration should result in only fine-tuning to circuit, as well as a way to check that installation is successful.
  • Page 15: Exit Maintenance Menu

    Maintenance Menus 5.2.2 Zero Adjust The ZERO function must be performed by exposing the AM-5150 instrument to clean fresh air. If the air at the sensor is in question, use a cylinder of 20.9% oxygen to provide a clean air reference.
  • Page 16: Gas Span

    4. Open the valve to apply the calibration gas to the sensor. An auto detect sequence is initiated after 30 seconds, the AM-5150 will monitor the cal reading for stability. 5. Watch for the signal level to stabilize. This should take about 1 – 4 minutes.
  • Page 17: Alarm Set Points

    Software revision may cause variations of display output. 5.2.5 mA Span Set The AM-5150 4-20mA span range is set at the factory, normally to the full scale of the measurement and can be changed within limits. To change the span range: Enter the maintenance menu as shown in Figure 7 AM-5150 Maintenance Menu flow chart.
  • Page 18: Sensor Replacement

    ROCEDURE ARNING Power must be removed from the AM-5150 before this or any internal procedure. Failure to do so may cause damage to equipment, bodily injury or death. 1. Obtain a new sensor assembly. Make sure the sensor type is identical to your original sensor Sensor marking is on side of sensor see Figure 9 (Example: 813-4 the first 3 digits are sensor ID the 4 digit indicates a 4-wire sensor).
  • Page 19: Sensor Replacement Calibration

    Span function sets the sensitivity of the instrument. Initial Calibration: Wait at least 3 – 4 hours after initially supplying power to the AM-5150 instrument before initial calibration, overnight is preferred. The AM-5150 has been pre-calibrated at the factory, and initial field calibration should result in only fine-tuning to circuit, as well as a way to check that installation is successful.
  • Page 20: Accessory And Replacement Parts

    03034-832 Zero Gas, 20.9% O2, 17 liter 03296-209 Span Gas Contact ENMET for part number Cylinder of Calibration Gas of target gas for each instrument. See note below. : The gases should be identical, or equivalent (correlation gas) to those used to initially calibrate the unit, unless you want to recalibrate to a new gas or different concentration.
  • Page 21: Warranty

    ENMET shall not be liable for any loss or damage caused by the improper use of the product. The purchaser indemnifies and saves harmless the company with respect to any loss or damages that may arise through the use by the purchaser or others of this equipment.
  • Page 22 734.761.1270 Fax 734.761.3220 Returning an Instrument for Repair ENMET instruments may be returned to the factory or any one of our Field Service Centers for regular repair service or calibration. The ENMET Repair Department and Field Service Centers also perform warranty service work.