Page 1
Gain, Integral Time, and Differential Time) and will need to be field-tuned. Damper Area in which constant pressure is desired Damper Air Flow Pressure Transducer Damper 4-20 mA Feedback For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192 Page: 1 of 6...
Page 2
IICC. Note: When using a 4-20 mA signal as feedback into the V/I terminal, be sure to set SW 301 to “I”. For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192 Page: 2 of 6...
Page 3
Parameter F360 should be set to. In most cases, the feedback signal from the transducer is a 4-20 mA signal and F360 should be set to “1: V/I”. For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192 Page: 3 of 6...
Page 4
desired setpt units ASD Setpoint Upper Limit units units For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192 Page: 4 of 6...
Page 5
ASD Setpoint = 12 Hz Examples: Note: These values are starting point suggestions for tuning. They may or may not get the desired result right away. For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192 Page: 5 of 6...
Revision History Rev. Date Written/Revised Approved By Description 6/23/2011 Joshua Austin Terry Voigt Formatting. Revised to incorporate document control requirements. For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192 Page: 6 of 6...