The following example shows how to calculate the setpoint on a pressure control system with the
following transducer characteristics:
Pressure Transducer Range:
Transducer Output:
Desired Pressure:
Examples:
Note: These values are starting point suggestions for tuning. They may or may not get the desired
result right away.
For additional assistance, please contact Toshiba Adjustable Speed Drive Marketing Dept. at (800) 872-2192
0-300 PSI
4-20 mA
60 PSI
ASD Setpoint
300
PSI
ASD Setpoint = 12 Hz
Page: 5 of 6
60
PSI
60
Hz
0
PSI