PRODUCT SIZE
DN 25, 50, 80, 100, and 150 /
NPS 1, 2, 3, 4, and 6
Pressure Equipment Directive (PED)
Categories and Fluid Group
According to EN 14382, only in integral strength type
and Class A configuration (when both overpressure
and underpressure protections are set up) this
slam- shut valve can be classified like a safety
accessory according to PED.
The minimum PS between SSD valve and controller
shall be the PS of the safety accessory to comply the
provisions of EN 14382 about integral strength type.
This product, in its Class A and integral strength
configuration, is a safety accessory for pressure
equipment in the following PED 2014/68/EU
categories on Table 1.
Built-in pressure accessories (e.g. controllers
Types OS/80 and OS/80-X) conform to
PED Article 4 section 3 and were designed and
manufactured in accordance with sound engineering
practice (SEP).
Per Article 4 section 3, these "SEP" products must not
bear the CE marking.
Figure 2. Type BM5A Slam-Shut Valves Nameplate
Table 1. PED Category for Type BM5A Slam-Shut Valves
CATEGORY
Note 1:
See Body Size and End Connection Style
Note 2:
Year of manufacture
Note 3:
Class A or Class B
Only valves with overpressure and underpressure settings can be classified
in Class A.
Note 4:
Class 1: -10 to 60°C / 14 to 140°F
Note 5:
Maximum Allowable Pressure (PS)
CL300 RF: 50 bar / 725 psig
CL600 RF: 100 bar / 1450 psig
IV
ATEX Requirements
If the provisions of EN 12186 and
EN 12279, national regulations or any
specific manufacturer recommendations
are not put into practice before
installation and if purge by inert gas
is not carried out before equipment's
start-up and shut-down operations,
a potential external and internal
explosive atmosphere can be present in
equipment and gas pressure regulating,
measuring stations or installations.
If a presence of foreign material in the pipelines is
foreseen and purge by inert gas is not carried out,
the following procedure is recommended to avoid any
possible external ignition source inside the equipment
due to mechanical generated sparks:
• Drainage to safe area via drain lines of foreign
materials, if any, by inflow of fuel gas with low
velocity in the pipe-work (5 m/sec.)
Type BM5A