8.
Rectifier start up and
shutdown.
All protections or switches of the system has to be in «Off»
position, and in particular the one belonging to batteries in
the equipment (F/Q3) and its homologous (F/Q8) in the
battery cabinet, in case there were an external battery set.
As the fuses are supplied inserted in the fuse holder,
to avoid misleading and losses, it is important to check
that the switches are opened (Off).
Check that it has been respected the stated in section 7 In-
stallation.
With loads shutdown, turn on the commercial power supply
to the input terminals:
ˆ For single phase equipments, terminals (X1) and (X4).
ˆ For three phase equipments, terminals (X1), (X2), (X3)
and (X4).
8.1.
First commissioning or after a
complete shutdown.
Ignore any manoeuvring of the not available switches or pro-
tections in your system.
Turn the protection or switch (F/Q3) and/or (F/Q8) to «On».
Battery protection of the system and/or battery cabinet
IS NOT A LOAD BREAK TYPE SWITCH. Do not turn
it meanwhile the system is supplying output voltage through
the batteries.
Turn the input or general input protection (F/Q1A) to «On».
In systems with single input protections (F/Q1B.. F/Q1*) for
each module, turn them «On».
In systems with single output protections (F/Q2B.. F/Q2*) for
each module, turn them «On».
Turn the general output protection (F/Q2A) to «On».
Output switch of the system IS NOT A LOAD BREAK
TYPE SWITCH.
Turn the output or general outgoing distribution protection
(F/Q2) to «On».
Turn the outgoing distributions protections (F/Q6A.. F/Q6*)
to «On».
The own leds of each module will light according to the status
of each rectifier. See section 9.
The system has a control module described in the user's
manual EN021*. By means of itself, the DC Power-S can be
managed and monitored and control the operating mode.
Start up the loads.
SALICRU
8.2.

Shutdown of the system.

Ignore any manoeuvring of the not available switches or pro-
tections in your system.
Shutdown the loads.
Turn the outgoing distributions protections (F/Q6A.. F/Q6*)
to «Off».
Turn the output or general outgoing distribution protection
(F/Q2) to «Off» .
Turn the general output protection (F/Q2A) to «Off».
Output switch of the system IS NOT A LOAD BREAK
TYPE SWITCH.
In systems with single output protections (F/Q2B.. F/Q2*) for
each module, turn them «Off».
In systems with single input protections (F/Q1B.. F/Q1*) for
each module, turn them «Off».
Turn the input or general input protection (F/Q1A) to «Off».
Turn the protection or switch (F/Q3) and/or (F/Q8) to «Off».
Battery protection of the system and/or battery cabinet
IS NOT A LOAD BREAK TYPE SWITCH. Do not turn
it meanwhile the system is supplying output voltage through
the batteries.
37