Salicru DC POWER-S DC-36-S User Manual page 35

Table of Contents

Advertisement

Internal connection side
ABAB
ABABABAB
4
2
1
•••
Client connection side (cable entry through the base of the cabinet)
Pin A1.- Contact normally closed (NC).
Pin B1.- Contacto normally opened (NO).
Pin A3 y B3.- Common.
Pin-out of the double tier terminal strip.
Internal connection side
6
4
2
1
3
•••
5
Client connection side (cable entry through the base of the cabinet)
Pin 3.- Contact normally closed (NC).
Pin 5.- Contact normally opened (NO).
Pin 1.- Common.
Pin-out of the triple tier terminal strip.
Fig. 23. Pin-out of the auxiliary contact terminal strip of the cabinet
of the system.
Auxiliary terminal
reference
(X40)
Input.
(X41A.. 41*)
Input individual protection of each module.
Batteries.
(8)
(X42)
(8)
Battery positive (+).
(X42A)
Battery negative (–).
(8)
(X42B)
(X44A.. 44*)
Output individual protection of each module.
(X45)
General output.
(X46)
Output or general outgoing distribution.
(X46A.. 46*)
Outgoing distribution.
(8)
For equipments with floating output:
When the physical protection means a single element (circuit breaker),
there will be one auxiliary contact only, so there will be a single group
of terminals only (X42). If the protection is done by fuses, the will be
two auxiliary contacts, one for each pole, so there will be two groups
of terminals (X42A) and (X42B) for the selective identification, as it is
shown in Fig. 23.
For equipments with the positive or negative output earthed:
In this case, as the protection will be single pole, there will be only one
group of terminals for the auxiliary contact (X42), corresponding to the
alive pole (the one not connected to earth).
Table 2.
Correlation between auxiliary terminals and the function of
the protection or switch, of the cabinet of the system.
SALICRU
ABABABAB
AB
•••
•••
•••
•••
Protection or switch function
7.10. Terminal strip, auxiliary contacts
of the protections of the battery
cabinet.
As an option the battery protection of the DC Power-S battery
cabinet can incorporate auxiliary contacts (C-NC-NO).
This auxiliary contact is supplied connected to a terminal
strip of double or triple tier (see Fig 24) and they have the
function to inform about the tripping or manoeuvring of the
protections. This information can be used to trigger , i.e., an
external alarm owned by the client.
Internal connection side
4
2
1
3
Client connection side (cable entry through the base of the cabinet)
Pin A1.- Contact normally closed (NC).
Pin B1.- Contacto normally opened (NO).
Pin A3 y B3.- Common.
Pin-out of the double tier terminal strip.
Internal connection side
Client connection side (cable entry through the base of the cabinet)
Pin 3.- Contact normally closed (NC).
Pin 5.- Contact normally opened (NO).
Pin 1.- Common.
Pin-out of the triple tier terminal strip.
Fig. 24. Pin-out of the auxiliary contact terminal strip of the battery
cabinet.
The voltage and current features that can support these con-
tacts are 250 V AC 1 A. Use cables of 1 mm
as minimum, but better to use 2,5 mm
the auxiliary terminals.
Table 3 shows the correlation of the auxiliary terminals with
the function of the protection. If the equipment does not have
the auxiliary contact ignore that reference.
ABAB
6
4
2
1
3
5
cross section
2
, to connect them to
2
35

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents