Siemens QBM3700 Series User Manual page 14

Modbus air pressure sensor with i/o extension
Table of Contents

Advertisement

3
Engineering
Modbus registers
Addr.
Description
4x0001
Type
4x0002
Error code
4x0003
Analog output coupling
4x0004
Differential pressure 1- Reliability
4x0005
Differential pressure 1 - Value
4x0006
Differential pressure 2- Reliability
4x0007
Differential pressure 2 - Value
4x0008
Analog input 1 - Reliability
4x0009
Analog input 1 - Value
4x0010
Analog input 2 - Reliability
4x0011
Analog input 2 - Value
Analog input 1
Addr.
Description
4x0020
Reliability.
4x0021
Value
4x0022
Sensor type AI1
Analog output 1
Addr.
Description
4x0027
Value
4x0028
Dependency

4x0029
Scaling low - (0.0V)
4x0030
Scaling high - (10.0V)
14 | 20
Unit
Scaling
R/W Area
1
R
1
R
1
R/W 0 = Analog output coupled with differential
1
R
See
R
config.
1
R
See
R
config.
1
R
°C / mV
0.1 / 1
R
1
R
°C / mV
0.1 / 1
R
Unit
Scaling
R/W Area
1
R
°C / mV
0.1 / 1
R
1
R/W 0 = No sensor (default)
Unit
Scaling
R/W Area
mV
1
R/W 0 ≤ VAL ≤ 10500
1
R/W 0 = Value @ 4x0027 = default if 4x0003=1
mV
1
R/W 0 ≤ VAL < Scaling high (0 = Default)
mV
1
R/W Scaling low < VAL (10000 = Default)
9705 = 1x 500 Pa
9710 = 1x 1250 Pa
9720 = 1x 2500 Pa
pressure sensors = default
1 = Analog output coupled as defined in
4x0028/4x0058 (setpoint)
1 = PT1000
2 = LG-Ni 1000
3 = NTC 10 k
4 = NI 1000
5 = 0...10 V
1 = With analog output 1
2 = With analog output 2
3 = With pressure sensor 1 = default if
4x0003=0
4 = With pressure sensor 2
Data type
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
uint16_t
int16_t
uint16_t
int16_t
Data type
uint16_t
int16_t
uint16_t
Data type
uint16_t
uint16_t
uint16_t
uint16_t
A6V11841988_en--_b

Advertisement

Table of Contents
loading

Table of Contents