Service Screen

12.2 Service Screen (NGA Tab - Page 1) Options

On the NGA tab screen, the blue text that appears functions as hyperlinks. The links function in two
different ways:
The following settings are simple ON/OFF selections:
– Global report
– Global reset
– Multiple Trouble Acknowledge
– Silencing
Tap any of these links to toggle the feature on or off.
Use the following links to open the Numeric Entry Keypad screen to enter user input or change
the selected setting.
– Address settings:
– Baud rate settings
The following settings are available from the NGA tab of the Service screen. Most of these settings
may also be changed by using the CAMWorks programming software, except the following:
Address Settings
Table 12.2.1 describes the links that appear on the Service, NGA tab screen.
Service Screen
(NGA Tab) Options
Multiple Trouble
Acknowledge
Silencing
Global Report
Global Reset
Address Settings
Baud Rate Settings
NEXT
42
Enables or disables the NGA's capacity to acknowledge
multiple trouble events with one touch of the "ACK" button. If
this button is enabled, up to ten troubles may be
acknowledged with one touch. If this button is disabled, only
one trouble will be acknowledged when the "ACK" button is
pressed.
Enables or disables the NGA's capacity to silence outputs
during alarms.
If enabled, the NGA will report events from all network nodes
regardless of their region membership. If disabled, the NGA
will only report events from other nodes within its region.
If enabled, the NGA will reset all nodes in the network. If
disabled, the NGA will only reset other nodes within its region.
This setting changes the network node address of the NGA.
This number may range from 1-64.
This setting changes the baud rate of the NGA's serial port.
Standard rates ranging from 1200 Baud to 115,200 Baud may
be selected. The baud rate must be set to 115,200 Baud in
order to perform downloads via the NGA's serial port.
If you select this link, the second page of the NGA tab
appears. Use this page to make changes to the Secondary
Settings screen.
Table 12.2.1 Service Screen (NGA Tab - Page 1) Links