Walk/Drill Screen

7.5 Walk/Drill Screen (Silent Walk Test Tab)

The screen that appears on the Silent Walk Test tab is similar to the Main Walk/Drill screen.
Table 7.5.1 describes the buttons that appear on the Silent Walk Test screen.
Walk/Drill
Screen Buttons
Test On
NOTE:
with the word, "Test" appended to the Event Report. All other trouble conditions will be
reported normally.
Test Off
WARNING:
!
Walk Test must be turned off ONLY from the same node that initiated the Walk Test.
28
This button turns on the Silent Walk Test function for the selected
region.All nodes in the region will produce a trouble condition, and set
their Walk/Drill bit in their system status map.During Silent Walk Test,
alarm and supervisory conditions do not produce a response from the
system. Instead, the events will be logged to the System Event Log,
displayed and printed out to a serial printer or computer if connected to
the system. SLC device troubles will be reported in a similar manner.
However, all other trouble conditions will be reported normally.
During Walk Test, trouble conditions related to SLC devices will be reported
This button turns off the Silent Walk Test function for the selected
region. The Walk Test trouble condition will be restored on all nodes in
the region and the Walk/Drill bit will be cleared for all nodes in the
region.
Table 7.5.1 Walk/Drill Screen (Silent Walk Test Tab) Buttons