17) Tone Table
Tone Selection
–
To select the required first stage tone set the tone switches 1 to 6 (see Fig 10) to the tone setting shown in the table below. The table also shows
nd
rd
th
which 2
, 3
and 4
stage tones are available for use with the selected first stage tone if more than one tone output stage is required.
Stage 1
Tone Description
Tone No
1
1000Hz PFEER Toxic Gas
1200/500Hz @ 1Hz DIN /
2
PFEER P.T.A.P.
1000Hz @ 0.5Hz(1s on, 1s
3
off) PFEER Gen. Alarm
1.4KHz-1.6KHz 1s, 1.6KHz-
4
1.4KHz 0.5s NF C 48-265
544Hz(100mS)/440Hz
5
(400mS) NF S 32-001
1500/500Hz - (0.5s on , 0.5s
6
off) x3 + 1s gap AS4428
500-1500Hz Sweeping 2 sec
7
on 1 sec off AS4428
500/1200Hz @ 0.26Hz(3.3s
on, 0.5s off) Netherlands -
8
NEN 2575
1000Hz (1s on, 1s off)x7 + (7s
9
on, 1s off) IMO Code 1a
1000Hz (1s on, 1s off)x7 + (7s
10
on, 1s off) IMO Code 1a
420Hz(0.5s on, 0.5s off)x3 +
1s gap ISO 8201 Temporal
11
Pattern
1000Hz(0.5s on, 0.5s off)x3 +
1s gap ISO 8201 Temporal
12
Pattern
422/775Hz - (0.85 on, 0.5
off) x3 + 1s gap NFPA -
13
Temporal Coded
1000/2000Hz @ 1Hz
14
Singapore
15
300Hz Continuous
16
440Hz Continuous
17
470Hz Continuous
500Hz Continuous IMO code
18
2 (Low)
19
554Hz Continuous
20
660Hz Continuous
21
800Hz IMO code 2 (High)
22
1200Hz Continuous
23
2000Hz Continuous
24
2400Hz Continuous
440 @0.83Hz (50
25
cycles/minute) Intermittent
470 @0.9Hz - 1.1s
26
Intermittent
470Hz @5Hz - (5
27
cycles/second) Intermittent
544Hz @ 1.14Hz - 0.875s
28
Intermittent
655Hz @ 0.875Hz
29
Intermittent
660Hz @0.28Hz - 1.8sec on,
30
1.8sec off Intermittent
660Hz @3.34Hz - 150mS on,
31
150mS off
Intermittent
__________________________________________________________________________________________________________________
European Safety Systems Ltd. Impress House, Mansell Road, Acton, London W3 7QH
Document No. D211-00-601-IS
Tone Visual
1000Hz
1200Hz
500Hz
1000Hz
1s
1600Hz
1400Hz
1s
544Hz
0.1s
440Hz
1500Hz
0.5s 0.5s
500Hz
1500Hz
500Hz
1200Hz
500Hz
1000Hz 1s
1s
1s
1s
1s
1s
1s
1s
420Hz 0.5s
0.5s
0.5s
1000Hz 0.5s
0.5s
0.5s
775Hz
422Hz
0.85s
0.5s
0.85s
2000Hz
1000Hz
300Hz
440Hz
470Hz
500Hz
554Hz
660Hz
800Hz
1200Hz
2000Hz
2400Hz
440Hz
0.6s
470Hz 0.55s
470Hz
0.1s
470Hz 0.43s
655Hz 0.57s
660Hz
1.8s
660Hz 0.15s
Issue: F
02-03-2020
1s
1s
0.5s
0.4s
0.5s 0.5s 0.5s
1.5s
2s
1s
0.5s
3.3s
7s
1s
1s
1s
1s
1s
1s
7s
0.5s
0.5s
1.5s
0.5s
0.5s
1.5s
0.5s
0.85s
1.5s
1s
0.6s
0.55s
0.1s
0.44s
0.57s
1.8s
0.15s
sales@e2s.com
www.e2s.com
Sheet 8 of 9
Stage 2
Stage 3
Switch Settings
Tone
Tone
1 2 3 4 5 6
(S2)
(S3)
0 0 0 0 0 0
3
2
1 0 0 0 0 0
1
3
0 1 0 0 0 0
1
2
1 1 0 0 0 0
44
24
0 0 1 0 0 0
52
19
1 0 1 0 0 0
7
44
0 1 1 0 0 0
6
44
1 1 1 0 0 0
44
24
0 0 0 1 0 0
18
34
1 0 0 1 0 0
21
34
0 1 0 1 0 0
44
1
1 1 0 1 0 0
44
1
0 0 1 1 0 0
44
1
1 0 1 1 0 0
23
3
0 1 1 1 0 0
44
24
1 1 1 1 0 0
44
24
0 0 0 0 1 0
44
24
1 0 0 0 1 0
44
24
0 1 0 0 1 0
64
24
1 1 0 0 1 0
44
24
0 0 1 0 1 0
44
24
1 0 1 0 1 0
44
24
0 1 1 0 1 0
15
3
1 1 1 0 1 0
48
20
0 0 0 1 1 0
1
44
1 0 0 1 1 0
1
44
0 1 0 1 1 0
1
44
1 1 0 1 1 0
44
24
0 0 1 1 1 0
1
44
1 0 1 1 1 0
44
24
0 1 1 1 1 0
30
24
Tel: +44 (0)208 743 8880
Fax: +44 (0)208 740 4200
Stage 4
Tone
(S2 + S3)
44
44
44
1
1
1
1
35
1
1
8
8
8
35
35
35
35
35
35
35
35
35
35
35
8
8
8
8
8
8
8
Need help?
Do you have a question about the D2 C2X05DC024 Series and is the answer not in the manual?