Wiring Functions; Table 3: Terminal Connections - FGD FlameSpec IR3-H2-HD User Manual

Triple ir flame detector
Table of Contents

Advertisement

FlameSpec IR3-H2-HD User Manual

4.1 Wiring Functions:

The detector has 20 terminals as defined in the following table:
Pin #
Function
Ground
Ground (earth)
24 VDC (+)
1
2
24 VDC (-)
3
0-20mA+ (In)
4
0-20mA- (out)
5
Fault Relay
6
Fault Relay COM
7
Alarm Relay (NO)
8
Alarm Relay COM
9
Analog Video +
10
Analog Video -
24 VDC (+)
11
12
24 VDC (-)
13
Manual BIT activation
14
RS 485 (+)
15
RS 485 (-)
Ethernet TX+
16
17
Ethernet TX-
18
Ethernet RX+
Ethernet RX-
19
20
Shield
For more information & Technical support: (+1) 714-671-8500 · support@fg-detection.com
T
3: T
ABLE
ERMINAL CONNECTIONS
Connected to a screw on the housing exterior.
Power supply (18-32 VDC)
Power supply return (0V)
This output is used for analog 0-20 mA current output
A normally open SPST contact relay, that is energized (closed) when the
detector is in normal operation, and opens in case of fault.
A normally open SPST contact relay, that is open in normal operation,
and closed when fire is detected. This relay can be configured to latch
as described in section (3.4).
Composite (analog) video output
Power supply (18-32 VDC)
Power supply return (0V)
The manual BIT (built-in test) can be initiated by momentarily short
circuiting this terminal and one of the "24 VDC (-)" terminals (2 or 12)".
See 3.8 Manual BIT – Alarm Output Test for more details.
RS-485 Modbus communication (used by the "FGD Communicator"
software)
Ethernet communication, used for digital video (with ONVIF profile S
protocol)
This terminal should be left connected to the housing internal ground
screw.
F140V0020.03