Eaton VCP-TL Series Instructions For The Use, Operation And Maintenance page 60

Linear magnetic vacuum circuit breakers
Table of Contents

Advertisement

Instruction Book
Page 54
Effective: May 2016
Table 6.4 Troubleshooting Guide (continued from previous page)
Symptom
Circuit breaker cannot be closed
locally, but can be closed remotely
Circuit breaker makes no attempt to
close with either local (manual) or
remote controls
Probable Cause
Controller or pushbutton switch
wiring problem
Circuit breaker interlock is
preventing close
Controller wiring problem
Damaged auxiliary switch or close
coil
For more information visit:
www.Eaton.com
Corrective Actions
Inspect for loose wires into con-
troller or open pushbutton switch
Make sure circuit breaker is fully
racked in or out on enclosure
(drawout only)
Verify that emergency open
handle is in a vertical position
Check all interlock switches for
obstructions
Inspect for loose wires into con-
troller
Contact EATON Service Center
IB131017EN