This parameters page is also a good place to check that all batteries are connected and working
properly. In see the individual battery data sheet for the normal working conditions, e.g. the current
limit per cell. For example, If each battery is rated to 25A charge current, and the menu shows a 75A
charge current limit ( 75 / 25 = 3 ) means there are 3 Pylontech battery modules connected.
Note that 'details' menu of the battery (e.g. Lowest and Highest cell voltages etc) is not currently
supported by Pylontech.
5. VEConfigure Settings
When using the latest firmware on all compatible connected devices, and once the battery module
has been detected by the GX device, battery charging parameters (e.g. Maximum Charge Current,
Target Battery Voltage, etc) are automatically configured by the Pylontech BMU, and communicated
to the rest of the Victron components in the system via DVCC.
It is possible to override some of these automatic settings to provide additional limitations (e.g.
reduce the total charge current that would be provided but the MultiPlus). The following information is
provided for that purpose, though is not required for the safe operation of the system.
This section presumes familiarity with
Voltages shown are for the 48V model, and should be scaled for the 24V model. The 24V model is an
8-series configuration while the 48V model is a 15-series configuration. Voltages should therefore be
scaled by 8/15.
5.1 General tab
Check the "Enable battery monitor" function
Set the battery capacity to the total capacity of the battery: eg 50Ah times the number of
battery modules for the 2000B Plus model.
The other parameters ("State of charge when bulk finished" and "Charge efficiency") can be left
to their default setting: They are ignored for a Pylontech installation.
5.2 Charge Settings
Charger tab
Parameter
Setting
Battery type
Lithium
Charge curve
Fixed
Absorption voltage 52.0 V
Float voltage
51.0 V
Absorption time
1 Hr
Note: make sure to double check the float voltage after completing Assistants, and if necessary set it