Fault Reset; Trial Operation - SAJ PDS33 Series User Manual

Solar pump controller
Hide thumbs Also See for PDS33 Series:
Table of Contents

Advertisement

PDS33 Series

4.2.2 Fault Reset

After the controller has failed, the controller will display the relevant fault code
information. The conventional fault code (Err02/3/4/5/6/7/8/9/10/11/12/18) can
automatically reset after 10s operation, and can also choose to reset the
STOP/RESET on the keyboard. If the conventional failure persists, the controller
will reset once every 10s. Special fault code (Err13/14) requires the user through
the STOP/RESET key on the keyboard to reset the fault; the controller can
continue to run after the reset.

4.3 Trial operation

●Check and make sure wiring are correct. If needed, take a megger to test the
insulation of motor, cable,
etc.;
●Use a multimeter to test the PV output voltage at the DC
switch.;
●Power on the controller by switch the DC switch.
●If necessary, modify and set the parameters of motor to the controller
For Example, if the motor which rated frequency is 60Hz, these parameters need
modification:
High limit of running frequency F0.12=60;
Other related parameters are: motor rated power F2.01, motor rated frequency
F2.04=60, motor rated speed F2.05, motor rated voltage F2.02, motor rated current
F2.03.
Note: default motor rated frequency setting is 50Hz.
Slowly start to check the direction
Pressing the RUN/STOP key to start the motor shortly and slowly, and check the
direction of the pump.
If the pump is in dry-run state, the maximum operating time cannot exceed 15s,
otherwise it may cause damage to the pump.