The model, serial number, features, power supply voltage, etc., are reported on the labels applied to the machine

1.3 ACCESSORIES

-
primary circuit double standard pump
-
secondary circuit standard pump (single or double in line with the primary circuit one/s)
-
primary circuit high head pressure pump (single or double)
-
secondary circuit high head pressure pump (single or double in line with the primary circuit one/s)
-
model for outdoor installation
-
panelled model for indoor installation
-
hydraulic pressure gauge for the primary circuit
-
rubber shock absorbers
-
wooden crate packaging
-
special slide for container shipment

1.4 FIELD OF APPLICATION

They must be used within the application limits stated in the TECHNICAL DOCUMENT.
Units with glycols:
Indoor version
Units containing glycols in the indoor version of the primary circuit are designed and built to operate at outdoor temperatures
between +3° C and +45° C. They therefore do not provi de the installation of heating cables to protect the internal
components. For operation at temperatures outside of the aforementioned range, it is necessary to contact our Technical
Office.
Outdoor version
Units containing glycols in the outdoor version of the primary circuit are designed and built to operate within the following
limits, whose values depend on the percentage of glycol in the primary circuit.
With a 20% concentration of ethylene glycol, the minimum admissible temperature is -5° C
With a 30% concentration of ethylene glycol, the minimum admissible temperature is -10° C
With a 40% concentration of ethylene glycol, the minimum admissible temperature is -20° C
The overall maximum admissible temperature is 45° C