When twin mode is enabled, if only one single lack of water external contact is
used for both units (terminals 13-14 for the single-phase version, terminals 11-12
for the three-phase version), two diodes must be inserted, making sure to comply
with the polarity between the contacts of the 2 units. Refer to figure 12.
Description
I/O terminals of the pump inverter (see Table 8)
External diode
Lack of water external contact
Parameter
Unit of
measurement
Adjustment type
SnG
NSt
FOL
[
,
,
]
Multi-pump twin
adjustment mode
BuP
ALt
PAr
[
,
,
,
FPA
]
Description
Adjustment type selection:
SnG
= single pump adjustment
NSt
= multi-pump twin adjustment, Master pump
FOL
= multi-pump twin adjustment, Follower pump
SnG
Default:
Multi-pump twin adjustment mode selection:
BuP
= Backup: only the Master pump is in operation. The
Follower pump only comes into operation in case of Master pump
fault
ALt
= Alternate operation: only one pump at the time is in
operation.
Pump operation switches regularly (parameter P57) in order to