13. VALUE OF THE RESISTANCE R AND OF THE RESISTANCE X
OF FAULT LOOP:
See EN60439-2 and CEI61439-6, below data for the application of the impedance method:
FAULT LOOP
Characteristics (Ω/m)
R
b20ph ph
R
b20ph N
R
b20ph PE
R
(1)
bph ph
R
(1)
bph N
R
(1)
bph PE
X
bph ph
X
bph N
X
bph PE
(1) at 35°C ambient temperature and maximal rated current.
Protection against short-circuits:
For intensities 130A, Icw<10kA.
For intensities 160A and 200A TR: Ipk=11kA.
14. INTENSITY ACCORDING TO DUTY CYCLE:
ambiant
Duty Cycle
Temperature
35°C
40°C
55°C
35°C
40°C
55°C
Mobilis Elite Technical Data
www.fels.fr
|
T +33(0)3 88 67 10 60
Intensity
130A
160A
0,00101
0,000699
0,00101
0,000699
0,00101
0,001048
0,00124
0,000865
0,00124
0,000865
0,00124
0,001297
0,000271
0,000271
0,000271
0,000271
0,000271
0,000271
Factor
40A
60A
80%
72A
90A
80%
67A
86A
80%
48A
63A
100%
68A
85A
100%
64A
82A
100%
47A
61A
|
F +33 (0)3 88 55 01 79
200A - TR
0,000505
0,000505
0,000757
0,000613
0,000613
0,000919
0,000271
0,000271
0,000271
Intensity
100A
130A
117A
127A
109A
117A
86A
87A
114A
120A
106A
109A
82A
83A
|
Edité le 04/01/2017
160A
200A
162A
211A
155A
195A
131A
140A
152A
184A
145A
171A
121A
126A
Page 25/223