Night Low Noise Function - LG MULTI V M ARNU07GTU 4 Series Svc Manual

Table of Contents

Advertisement

4.3 Night Low Noise Function

In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of ODU at night
which has low cooling load.
Night low noise function setting method
RPM / Time Settings
Step
Judgment Time(hr)
op1
8
op2
6.5
op3
5
op4
8
op5
6.5
op6
5
op7
8
op8
6.5
op9
5
op10
op11
Continuous operation
op12
op13
6.5
op14
6.5
op15
6.5
CAUTION
• Request installer to set the function during installation.
• In case the function is not used, set the dip S/W OFF and reset the power.
• If ODU Hz and RPM change, cooling capacity may go down.
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button : "Func" Push
the '●' button
Select the Function using '▶', '◀' Button : "Fn3"
Push the '●' button
Select the Option using '▶', '◀' Button : "op1~op13"
Push the '●' button
Start the Night low noise function :
Save the selected option value in EEPROM
Operation Time(hr)
9
10.5
12
9
10.5
12
9
10.5
12
10.5
10.5
10.5
- 27 -
Copyright © 2018 LG Electronics Inc. All rights reserved.
Only training and service purposes.
Function

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Multi v m arnu09gtu 4 seriesMulti v m arnu12gtu 4 seriesMulti v m arnu18gtt 4 seriesMulti v m arnu24gtt 4 seriesMulti v m arnu05gtr 4 seriesMulti v m arnu07gtr 4 series ... Show all

Table of Contents