Night Low Noise Function - LG MULTI VS AARUN040LSS5 Installation Manual

Table of Contents

Advertisement

Night Low Noise Function

In cooling mode, this function makes the ODU fan operate at low RPM to reduce the fan noise of
ODU at night which has low cooling load.
Night low noise function setting method
Time Settings
Judgement
Step
Time(Hr)
op1
op2
6.5
op3
op4
op5
6.5
op6
op7
op8
6.5
op9
op10
continuous operation
op11
continuous operation
op12
continuous operation
op13
6.5
op14
6.5
op15
6.5
CAUTION
!
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.
Master unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn3" Push the '●' button
Select the Option using '▶', '◀' Button :
"op1~op15" Push the '●' button
Start the Night low noise function :
Save the selected option value in EEPROM
Operation
Time(Hr)
8
9
10.5
5
12
8
9
10.5
5
12
8
9
10.5
5
12
10.5
10.5
10.5
ELECTRICAL WIRING