High Static Pressure Compensation mode

This function secures the air flow rate of ODU, in case static pressure
has been applied like using duct at fan discharge of ODU.
Static pressure compensation mode setting method
Outdoor Unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn 2" Push the '●' button
Select the Option using '▶', '◀' Button :
"oFF","oP1"~"oP3" Push the '●' button
Start the Static pressure compensation mode :
Save the selected option value in EEPROM
Settings
setting
oFF
oP1
oP2
oP3

Night Low Noise Function

In cooling mode, this function makes the ODU fan operate at low RPM
to reduce the fan noise of ODU at night which has low cooling load.
Night low noise function setting method
Outdoor Unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn 3" Push the '●' button
Select the Option using '▶', '◀' Button :
"oP1"~"oP12" Push the '●' button
Start the Night low noise function :
Save the selected option value in EEPROM
Time Settings
Step
Judgment Time(Hr)
oP1
oP2
oP3
oP4
oP5
oP6
oP7
oP8
oP9
oP10
oP11
oP12
Static pressure
0~20 Pa
21~40 Pa
41~60 Pa
61~80 Pa
Operation Time(Hr)
8
9
6.5
10.5
5
12
8
9
6.5
10.5
5
12
8
9
6.5
10
5
12
Continuous operation
Continuous operation
Continuous operation
Noise
Step
oP1~oP3, oP10
oP4~oP6, oP11
oP7~oP9, oP12
CAUTION
!
• Request installer to set the function during installation.
• If ODU RPM changes, cooling capacity may go down.

Overall defrost mode

Mode setting method
Outdoor Unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn 4" Push the '●' button
Select the Option using '▶', '◀' Button :
"on"~"oFF" Push the '●' button
Overall defrost mode is set
Mode setting
- on: Operate overall defrost
- oFF: Operate partial defrost
CAUTION
!
• Ask an authorized technician to setting a function.

Setting the ODU address

Mode setting method
Outdoor Unit PCB DIP switch on : No.5
Select the mode using '▶', '◀' Button :
"Func" Push the '●' button
Select the Function using '▶', '◀' Button :
"Fn 5" Push the '●' button
Select the Option using '▶', '◀' Button :
"0"~"255" Push the '●' button
ODU address is set
CAUTION
!
• Ask an authorized technician to setting a function.
• If use a function, first install a Central controller.
Noise reduction (dB)
-3
-6
-9