Sequence Of Operation - Automatic Mode - Isolation Ats - ABB Zenith ZT30 Operation And Maintenance Manual

Short-time rated ats and bypass isolation ats
Table of Contents

Advertisement

Sequence of Operation -
Automatic Mode - Isolation ATS
Standard Transition
Source 1 Power Failure:
When Source 1 voltage or frequency has fallen below the preset
"Fail" values, the controller initiates the Time Delay Source 2
Start Timer (Engine Start Timer "P") cycle. Upon completion
of the (P) time delay, an Engine start Signal is sent to Source
2. When Source 2 voltage and frequency reach the preset
"Restore" Values, the time delay to Source 2 Timer (W) begins
its timing cycle to ensure voltage and frequency stabilization
before transfer. A manual pushbutton BYPASS is provided
to bypass the "W" time delay if desired. After the (W) time
delay, the MX controller initiates a transfer signal through the
SCR-E to operate the main transfer operator. The load is now
transferred to Source 2 line. The transfer switch is mechanically
locked. SN limit switch awaits the next operation to Source 1.
Restoration of Source 1 Power:
When Source 1 power reach the preset "Restore" values,
the controller initiates re-transfer to Source 1 sequence.
The delay to Source 1 Timer (T) begins its timing cycle to
ensure voltage and frequency stabilization before retransfer.
A manual pushbutton BYPASS is provided to bypass the "T"
time delay if desired. After the (T) time delay, the MX controller
initiates a transfer signal through the SCR-N to operate the
main transfer operator. The load is now transferred to Source
1 line. The transfer switch is mechanically locked. SE limit
switch awaits the next operation to Source 2. Immediately
after re-transfer, the S2 Stop Delay Timer (Delay to Engine
Stop "U") begins its cycle to allow Source 2 Engine to run
unloaded. A manual pushbutton BYPASS is provided to
bypass the "U" time delay if desired. Upon completion of the
(U) timing cycle, the controller sends an Engine stop signal.
Zenith Automatic Transfer Switch |
new.abb.com/low-voltage
Delayed Transition
Source 1 Power Failure:
When Source 1 voltage or frequency has fallen below the preset
"Fail" values, the controller initiates the Time Delay Source 2
Start (Engine Start Timer "P") cycle. Upon completion of the (P)
time delay, an Engine start Signal is sent to Source 2. When
Source 2 voltage and frequency reach the preset "Restore"
values, the time delay to open Source 1 timer (W) begins its
timing cycle to ensure voltage and frequency stabilization
before re-transfer. A manual pushbutton BYPASS is provided
to bypass the "W" time delay if desired. After the (W) time
delay, the MX controller initiates a transfer signal through
the SCR-NO to operate the main transfer operator. The load
is now transferred to the Open position. The time delay to
Source 2 timer (DW) begins its timing cycle. After the (DW) time
delay, the MX controller initiates a transfer signal through the
SCR-E to operate the main transfer operator. The load is now
transferred to Source 2 line. The transfer switch is mechanically
locked. SN limit switch awaits the next operation to Source 1.
Restoration of Source 1 Power:
When Source 1 power reach the preset "Restore" values,
the controller initiates re-transfer to Source 1 sequence. The
delay to open Source 2 Timer (T) begins its timing cycle to
ensure voltage and frequency stabilization before retransfer.
A manual pushbutton BYPASS is provided to bypass the "T"
time delay if desired. After the (T) time delay, the MX controller
initiates a transfer signal through the SCR-EO to operate the
main transfer operator. The load is now transferred to the
Open position. The time delay to Source 1 timer (DT) begins
its timing cycle. After the (DT) time delay, the MX controller
initiates a transfer signal through the SCR-N to operate
the main transfer operator. The load is now transferred to
Source 1 line. The transfer switch is mechanically locked.
SE limit switch awaits the next operation to Source 2.
Immediately after re-transfer, the S2 Stop Delay Timer (Delay
to Engine Stop "U") begins its cycle to allow Source 2 Engine
to run unloaded. A manual pushbutton BYPASS is provided to
bypass the "U" time delay if desired. Upon completion of the
(U) timing cycle, the controller sends an Engine stop signal.
25