SPECIFICATIONS
Functional Characteristics
Adjustments/Settings
Overcurrent
Underload (dry-well)
Overvoltage
Undervoltage
Number of restarts allowed in a 60-
second period (rapid-cycling)
Trip Delay Times
Overcurrent
Dry well
Reset DelayTime
Over/undervoltage
All Other Faults
Input Characterisitcs
Supply Voltage
Load Range
Frequency
Output Characteristics
Output Contact Rating—SPST
General Characteristics
Maximum Input Power
Weight
Standards Passed
Electrostatic Discharge (ESD)
Ambient Operating Temperature
1
NOTE: 50Hz will increase all delay timers by 20%
© 2009 SymCom, Inc. All Rights Reserved
125% of calibration point
Adjustable 70-90% of calibrated run power
265VAC
190VAC
4
5 seconds
4 seconds
2 seconds
Manual, 2-225 minutes
230VAC
1/3 – 3hp
1
50
/60Hz
3hp, 240VAC (17 amps max.)
5 W
14 oz.
IEC 61000-4-2, Level 2, 4kV contact, 6kV air
-40° to 70°C (-40° to 158°F)
9