SPECIFICATIONS
3 - Phase Line Voltage
Frequency
Low Voltage (% of setpoint)
Trip
Reset
High Voltage (% of setpoint)
Trip
Reset
Voltage Unbalance (NEMA)
Trip
Reset
Trip Delay Time
Low, High, and Unbalanced Voltage
Single-phasing faults (>25% UB)
Restart Delay Time
After a fault or complete power loss
Output Contact Rating - SPDT
Pilot Duty
General Purpose
Power Consumption
Weight
Enclosure
Terminal
Torque
Wire AWG
Safety Marks
UL
CE
Standards Passed
Electrostatic Discharge (ESD)
Radio Frequency Immunity, Radiated 159 MHz, 10 V/m
Fast Transient Burst
*NOTE: 50 Hz will increase all delay timers by 20%
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.clrwtr.com - Email: info@clrwtr.com
190 - 480 VAC
50* - 60 Hz
90% ± 1%
93% ± 1%
110% ±1%
107% ±1%
2 - 8% Adjustable
Trip Setting minus 1% (5 - 8%)
Trip Setting minus 0.5% (2 - 4%)
1 - 30 Seconds Adjustable
1 Second Fixed
1 - 500 Seconds Adjustable
480 VA @ 240 VAC
10 A @ 240 VAC
6 Watts (maximum)
14 oz
Polycarbonate
6 Inch-Pounds Max.
12 - 20 AWG
UL508 (File # E68520)
IEC 60947-6-2
IEC 1000-4-2, Level 3, 6 kv contact,
8 kv air
IEC 1000-4-4, Level 3, 3.5 kv input
power and controls