Download Print this page

Cisco 6160 Installation Procedures Manual page 11

Without a pots splitter configuration

Advertisement

Chapter 4
Installing a Cisco 6160 Without a POTS Splitter Configuration
Use the flat-head screwdriver and a clockwise motion to tighten the ground screw in the power terminal
Step 8
block connector. Pull gently on the wire to ensure that it is held firmly in place.
to ground the Cisco 6160 chassis from the power terminal block connector.
Figure 4-7
Step 9
Connect the other end of the grounding wire to an appropriate grounding point at your site or to the rack.
(see
Figure
a.
Remove all paint or oxidation from the rack at the point of the grounding connection.
b.
Use a 3/16-inch flat-head screwdriver to loosen the grounding screw on the rack.
c.
Connect the wire to a ring lug (large enough for the rack screw to fit through).
d.
Use a 3/16-inch flat-head screwdriver and the screw to attach the ring lug to the rack.
Tighten the grounding screw on the rack over the ring lug (see
e.
If you are connecting two power sources to the Cisco 6160 system, repeat
Step 10
second power terminal block.
Step 11
Repeat
OL-2190-02 B0
Grounding the Cisco 6160 Chassis from the Power Terminal Block Connector—Backplane
View
1
B R K R
P W R 1
4-7). To connect the grounding wire to the rack, complete the following steps:
Step 1
through
Step 10
for each Cisco 6160 chassis being installed.
Installation Procedures
Figure 4-7
Figure
4-7).
Step 1
through
Cisco 6160 Hardware Installation Guide
shows how
Step 9
for the
4-11

Advertisement

loading