Download Print this page

Cisco 6160 Installation Procedures Manual page 7

Without a pots splitter configuration

Advertisement

Chapter 4
Installing a Cisco 6160 Without a POTS Splitter Configuration
Locate the three grounding holes on the Cisco 6160 side panel.
Step 7
Cisco 6160 chassis using a grounding lug.
Figure 4-3
Match the holes in the grounding lug to the appropriately spaced pair of grounding holes on the side of
Step 8
the chassis. Use the top two holes for a 5/8-inch lug. Use the bottom two holes for a 3/4-inch lug.
Insert the screws through the holes in the lug and the chassis.
Step 9
Use a Phillips-head screwdriver to tighten the screws and secure the grounding lug firmly to the chassis.
Step 10
Connect the other end of the grounding wire to an appropriate grounding point at your site or to the rack
Step 11
(see
Figure
Remove all paint or oxidation from the rack at the point of the grounding connection.
a.
Use a 3/16-inch flat-head screwdriver to loosen the grounding screw on the rack.
b.
Connect the wire to a ring lug (large enough for the rack screw to fit through).
c.
Use a 3/16-inch flat-head screwdriver and the screw to attach the ring lug to the rack.
d.
Tighten the grounding screw on the rack over the ring lug.
e.
Repeat
Step 12
OL-2190-02 B0
Grounding the Cisco 6160 Chassis Using the Grounding Lug—Backplane View
4-3). To connect the grounding wire to the rack, complete the following steps:
Step 1
through
Step 11
for each Cisco 6160 chassis being installed.
Installation Procedures
Figure 4-3
shows how to ground the
Cisco 6160 Hardware Installation Guide
4-7

Advertisement

loading