Fresh Air For Combustion - ECR Dunkirk PWB Series Manual

Gas-fired hot water boilers
Table of Contents

Advertisement

Air openings to combustion area must
!
not be obstructed. Following instructions
below, adequate combustion air can be
maintained.
Provide combustion air and ventilation air in
accordance with the section "Air for Combustion and
Ventilation," of the National Fuel Gas Code, ANSI
Z223.1 / NFPA 54, or applicable provisions of local
building codes.
Provide make-up air where exhaust fans, clothes
dryers, and kitchen ventilation equipment interfere
with proper operation.
National Fuel Gas Code recognizes several methods
of obtaining adequate ventilation and combustion air.
Requirements of the authority having jurisdiction may
override these methods.
Engineered Installations. Must be approved by
authority having jurisdiction.
Mechanical Air Supply. Provide minimum of
0.35 cfm per Mbh for all appliances located
within space. Additional requirements where
exhaust fans installed. Interlock each appliance
to mechanical air supply system to prevent main
burner operation when mechanical air supply
system not operating.
All Indoor Air. Calculate minimum volume for all
appliances in space. Use a different method if
minimum volume not available.
A.
Standard Method. Cannot be used if known
air infi ltration rate is 0.40 air changes per
hour. See Table 1 for space with boiler only.
Use equation for multiple appliances.
Volume ≥ 50 ft
Table 1 - Minimum Room Volume, Indoor Air Only*
Standard
Input Mbh
Method
37.5
1875
70
3500
105
5250
140
7000
175
8750
210
10500
245
12250
280
14000
* Table values based on boiler only. Add volume for any additional appliances.

FRESH AIR FOR COMBUSTION

WARNING
x Total Input [Mbh]
3
Known Air Infi ltration Rate Method (Air Changes Per Hour)
0.1
7875
14700
22050
29400
36750
44100
51450
58800
B.
Known Air Infi ltration Rate. See Table 1
for space with boiler only. Use equation
for multiple appliances. Do not use an air
infi ltration rate (ACH) greater than 0.60.
Volume ≥ 21 ft
C.
Refer to National Fuel Gas Code for opening
requirements between connected indoor
spaces.
All Outdoor Air. Provide permanent opening(s)
communicating directly or by ducts with outdoors.
A.
Two Permanent Opening Method. Provide
opening commencing within 12 inches of top
and second opening commencing within 12
inches of bottom of enclosure.
B.
One Permanent Opening Method. Provide
opening commencing within 12 inches of top
of enclosure. Provide minimum clearance of
1 inch on sides/back and 6 inches on front
of boiler (does not supersede clearance to
combustible materials).
C.
Refer to National Fuel Gas Code for additional
requirements for louvers, grilles, screens and
air ducts.
Combination Indoor and Outdoor Air. Refer
to National Fuel Gas Code for application
information.
0.2
0.3
3938
2625
7350
4900
11025
7350
14700
9800
17375
12250
22050
14700
25725
17150
29400
19600
4
⁄ACH x Total Input [Mbh]
3
Direct communication with outdoors or
communicating through vertical ducts.
Provide minimum free area of 1 in² per 4
Mbh of total input rating of all appliances
in enclosure.
Communicating through horizontal ducts.
Provide minimum free area of 1 in² per 2
Mbh of total input rating of all appliances
in enclosure.
0.4
0.5
1969
1575
3675
2940
5513
4410
7350
5880
9188
7350
11025
8820
12863
10290
14700
11760
0.6
1313
2450
3675
4900
6125
7350
8575
9800

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents