7.3 - Water inlet/outlet connections

2-pipe version
4-pipe version

8 - FLexIbLe Water PIPes

Description
Flexible pipes are used to make the water connections.
Every branch of the system must therefore have an
isolating valve.
Insulation: cell foam rubber to M1 fire rating.
Minimum bending radius: 106 mm.
The flexible water pipes are designed to carry treated
or untreated water (maximum 40% concentration of
ethylene glycol or propylene glycol).
Maximum hot water temperature 90°C.
Operating pressure: maximum 10 bar.
Connections: G1/" threaded nut.
Length: 400 mm (unit outlet).
38 mm
Condensate drain Ø 12
Flexible pipes, 400 mm
Threaded nuts G1/2"
17

Advertisement