Alarm ID
Alarm
Name
400
System
Fault
410
Abnormal
Auxiliary
Power
411
AFCI
Self-Chec
k Failure
412
DC Arc
Fault
413
Abnormal
PV String
Connectio
n
Issue 02 (2017-09-15)
Alarm
Possible Cause
Severity
the inverter.
When you are grounding
the PV string, you do not
connect an isolation
transformer to the inverter
output.
Major
Cause ID = 1/3/21/23/27
An unrecoverable fault occurs
on a circuit inside the inverter.
Major
Cause ID = 4
The sampling control board
has an abnormal voltage,
which may be caused by the
following:
The internal power chip of
the sampling control board
is faulty.
The detection circuit
becomes faulty.
Major
Cause ID = 1/2/3
AFCI check fails.
Major
Cause ID = 1/2/3/4
The PV string cable is in poor
contact or with open circuits.
Major
Cause ID = 1
The PV string does not
properly connect to the MPPT1
circuit.
Cause ID = 2
The PV string does not
properly connect to the MPPT2
circuit.
Cause ID = 3
The PV string does not
properly connect to the MPPT3
circuit.
Huawei Proprietary and Confidential
Copyright © Huawei Technologies Co., Ltd.
9 System Maintenance
Suggestion
2. If the PV string is grounded,
check whether the inverter output
needs to connect to an isolation
transformer. If yes, connect the
transformer to the inverter.
Turn off the AC output switch and
DC input switch. Then turn on the
AC output switch and DC input
switch after 5 minutes. If the fault
persists, contact Huawei technical
support.
1. When the alarm is generated, the
inverter shuts down
automatically. When the fault is
rectified, the inverter starts
automatically.
2. If the fault persists, contact
Huawei technical support.
1. Turn off the AC output switch
and DC input switch. Then turn
on the AC output switch and DC
input switch after 5 minutes. If
the fault persists, contact Huawei
technical support.
2. Disable the AFCI function if you
are sure not to use it.
Check whether the PV string cable is
in poor contact or with open circuits.
If yes, reconnect the cable.
Check the PV string for reverse
connection and cross connection.
88