Connecting The Pe Cable - Huawei SUN2000 Series User Manual

Hide thumbs Also See for SUN2000 Series:
Table of Contents

Advertisement

SUN2000-(20KTL, 29.9KTL, 30KTL, 36KTL, 40KTL)-
M3
User Manual
Table 5-2 Cable description
No.
1
2
3
4
Note a: Five-core cables with a cross-sectional area of 5 x 35 mm
mm

5.3 Connecting the PE Cable

● Ensure that the PE cable is securely connected. Otherwise, electric shocks may
occur.
● Do not connect the neutral wire to the enclosure as a PE cable. Otherwise,
electric shocks may occur.
Issue 01 (2020-10-15)
Cable
Type
DC input
Common PV cable in the
power
industry
cable
(Recommended model:
PV1-F)
AC
Outdoor copper-core/
output
aluminum-core cable
power
cable
(Option
Two-core outdoor
al)
shielded twisted pair
Signal
(recommended model:
cable
DJYP2VP2-2x2x0.75)
PE cable
Single-core outdoor
copper-core cable
2
are not supported.
D ANGER
Copyright © Huawei Technologies Co., Ltd.
5 Electrical Connections
Recommended
Specifications
● Conductor cross-
sectional area: 4–6
2
mm
● Cable outer
diameter: 4.5–7.8
mm
● Conductor cross-
sectional area:
2
16-50 mm
outdoor copper-
core cable or 35-50
2
mm
outdoor
aluminum-core
cable
● Cable outer
diameter: 16–38
mm
● Conductor cross-
sectional area: 0.2–
2
1 mm
● Cable outer
diameter: 4–11 mm
Conductor cross-
sectional area ≥ 16
2
mm
2
or 5 x 50
Source
Prepare
d by
users
Prepare
d by
users
Prepare
d by
users
Prepare
d by
users
30

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents