Door Lock Release Time And Reminder Signal - Honeywell Tagalarm-Plus Mounting And Operating Instructions

Doorguard for mb panels bus-2
Table of Contents

Advertisement

Available languages

Available languages

Mounting and Operating Instructions Doorguard for MB panels BUS-2
10.4.2

Door lock release time and reminder signal

- Permanent release via operation:
1. Permanent release with manual activation:
Once deactivated, the door can be accessed any number of times without a reminder signal.
Activation is performed by way of manual operation using an ID pass card or key.
2. Permanent release with automatic activation:
Once deactivated, the door can be remain open for any length of time without a reminder signal.
Activation is performed automatically when the door is closed.
- Manual activation:
The door can be opened at any time after activation. If the permissible
door release time is exceeded (door open time minus door open signal),
a reminder signal is emitted every 20 seconds.
The Doorguard must then be manually reactivated (see graphic on the
right).
- Automatic activation:
This function is intended for temporary release. Exceeding the release
time results in an optical and acoustical message (see graphic below):
Door lock release : Period in which the door may be opened (Default setting: 1 minute) when the Doorguard
Door open time:
Door open signal:
Irrespective of the automatic activation, the state can be changed at all times via an operating function.
12
Required software: MB24/48/100 from V18.xx, MB-Secure fromV04.xx (see 1.2.2)
is inactive.
Period during which the door is permitted to remain open after authorized opening before
an optical and acoustical message is emitted.
(Default setting: 3 minutes).
This period indicates how long the reminder signal of the Doorguard is activated before
expiry of the door open period. During this period, the door can be closed without an
optical or acoustical message being emitted (Default setting: 2 minutes).