WIRING
Model 8053
PHASE
PHASE
PHASE
120
Neutral
120
Cap This
Neutral
277V
Cap This
Z201659-0N
PAGE 4
Alta Labs, Enercept, Enspector, Hawkeye, Trustat, Veris, and the Veris 'V' logo are trademarks or registered trademarks of Veris Industries, L.L.C. in the USA and/or other countries.
H8051/H8053
Typical 208/480 VAC 3Ø, 3- or 4-Wire Installation
PULSE OUTPUT LINE
Typical 240/120 VAC 1Ø, 3-Wire Installation
PULSE OUTPUT LINE
Typical 277 VAC 1Ø, 2-Wire Installation
PULSE OUTPUT LINE
©2011 Veris Industries USA 800.354.8556 or +1.503.598.4564 / support@veris.com
INSTALLATION GUIDE
Model 8051
ØB
ØA
ØC
120V
Neutral
120V
Black
Red
Yellow
Cap This
Neutral
277V
Black
Red
Yellow
Cap This
Alternative 277 VAC 1Ø, 2-Wire Installation
Neutral
277V
Black
Red
Yellow
Cap This
PULSE OUTPUT LINE
NOTE: Multiply output by 3 for
proper kWh indication
(Assuming balanced load)
PULSE OUTPUT LINE
NOTE: Multiply output by 2 for
proper kWh indication
(Assuming balanced load)
PULSE OUTPUT LINE
NOTE: Multiply output
by 2 for proper kWh
indication
PULSE OUTPUT LINE
NOTE: Wires are crossed through
the CT, each entering from
the opposite direction. This
arrangement does not require
multiplying the output data.