Installation Manual

4.0 ELECTRICAL INSTALLATION

Electrical work should be undertaken by a qualified electrician in
accordance with the wiring regulations.
IMPORTANT
Isolation - Before commencing work, make sure that the unit is
electrically isolated from the mains supply.
18
Removing Electrical Panel
Release the electrical panel from the fan plate.
19
Removing Terminal Cover
Remove the terminal cover.
20
Completing Connections
Clamp the cable and complete the connections.
21
Refitting Terminal Cover
Refit terminal cover before replacing the electrical panel.
Nuaire |
Western Industrial Estate
|
|
| nuaire.co.uk
Caerphilly
CF83 1NA
4.1 Electrical Consumption & Weights
Model
XS6WA supply & extract
XS9WA supply & extract
XS12WA supply & extract
*Values are for extract only at 50hz.
4.3 Electrical Specification
230V ~ 50Hz / 220V ~ 60Hz Class I. Motor thermally protected by
overload device. Cable: 1mm maximum or minimum Fuse: 3 amp (if fan
is supplied from a 5A lighting circuit, no local fuse is required).
Note: If 2 x 12 inch fans or 3 x 6 or 9 inch fans are used in the same
operating mode in the same room they should all be controlled from
the same MFC speed control. This avoids the possibility of one fan (if
speed controlled at a lower flow rate) being stalled by the other fan(s).
Adequate make-up air provision sufficient to provide ventilation in
accordance with building regulations is required in all rooms. This
should be checked during commissioning with all fans in the same room
running together in all possible configurations.
The automatic shutters, motor bearings should be frequently inspected
and maintained to ensure they open fully/operate satisfactorily. Use
of an RCD and fused spur with 1A, Bussmann TDC180, BS1362, fuse
(Farnell order no: 1123029) for 1 fan or 2A, Bussmann TDC180, BS1362
fuse (Farnell order no: 1123032) for 2 or 3 fans is recommended.
Always confirm airflow direction before commissioning.
4.4 Wiring diagrams
4.4.1 On / Off Switch Operation
22
Wiring - On / Off Switch
Double pole
Fuse
isolator
max. 3 amp
L
N
Connect link wire between L2 & L4 for extract
or Connect link wire between L2 & L3 for supply.
4.4.2 Integral Sensor Operation
23
Wiring - Integral Sensor
SL
(Switched Live)
Double pole
Fuse
isolator
max. 3 amp
L
N
Connect link wire between L2 & L4 for extract
or Connect link wire between L2 & L3 for supply.
Connect switched live signal to L5 for integral timer module.
18. 03. 20. Document Number 671051
XS WA
Input Power*
Weight
(W)
(kg)
Max.
Economy
38
20
4.7
50
37
6.5
100
70
9.4
L5
L4
or
L3
L2
L1
N
XS Fan unit
L5
L4
or
L3
L2
L1
N
XS Fan unit with
integral sensor
5