1.0 SAFETY INFORMATION
The provision of the electrical supply and the connection of the unit to the mains must be
carried out by a qualified electrician.
Isolate from power supply before removing any covers. During installation / maintenance ensure
all covers are fitted before switching on the mains supply.
All-pole disconnection from the mains as shown in the wiring diagram must be incorporated
within the fixed wiring and shall have a minimum contact separation of 3mm in accordance with
latest edition of the wiring regulations.
This unit must be earthed.
Ducting must be securely fixed with screws to the spigot to prevent access to live parts. Duct
runs terminating close to the fan must be adequately protected by suitable guards.
If the supply cord is damaged, it must be replaced by the manufacturer, its service agent or
similarly qualified persons in order to avoid a hazard.
Precautions must be taken to avoid the back-flow of gases into the room from the open flue of
gas or other fuel-burning appliances.
This appliance should not be used by children or persons with reduced physical, sensory or
mental capabilities or lack of experience and knowledge, unless they have been given supervision
or instruction concerning the safe use of the appliance by a person responsible for their safety.
Children shall not play with the appliance. Cleaning and user maintenance shall not be carried
out by children.
1.1 Symbols
GENERAL WARNING
Signifies a general warning regarding hazard specified by supplementary information.
ELECTRIC SHOCK
This unit must be completely electrically isolated before any panels are removed. Check
mains supply and control connections.
ROTATING PARTS
This unit contains fast moving rotational parts which may start automatically. It is the
sole responsibility of the installer to adequately guard these components.
REFER TO INSTRUCTION MANUAL
Read and understand the installation and maintenance manual before installing,
operating or maintaining this product.
Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk
Adapt Trend (T) Control
Supply & Extract Ventilation with Heat Recovery
Installation Manual
08. 12. 21. Document Number 671949
EMC Directive
2014/30/EU
LVD Directive
2014/35/EU
1

Advertisement

Table of Contents
loading
Need help?

Need help?

Do you have a question about the xboxer xbc+ and is the answer not in the manual?

Questions and answers

Subscribe to Our Youtube Channel

Summary of Contents for NuAire xboxer xbc+

  • Page 1 REFER TO INSTRUCTION MANUAL Read and understand the installation and maintenance manual before installing, operating or maintaining this product. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 2: Personal Protective Equipment

    (1/4 turn). Silencer Arrangement) Note: Bottom access unit (BA) Filters cannot be accessed from the side of the unit. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 3: Mechanical Installation

    Lower filter into filter well in the base space, (Figure 4) with the blanking panel re-positioned to suit. Tilt filter and remove through panel Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 4 LPHW or Electric Heater Battery Note: The unit is shipped with four G4 filters in place, two of which are included as spares. For F7 filters contact Nuaire. Note: The unit is shipped with four G4 filters in place, two of which are included as spares. For F7 filters contact Nuaire.
  • Page 5 2 attenuator flange connections are attached to every unit. Add 60mm to dimension 'A' to include both flanges for standard (no roof) † units. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 6 3.7 Flange Connector Dimensions (mm) Flange Connector INTAKE / SUPPLY / EXTRACT DISCHARGE Dimensions to Hole Centres (mm) Unit Code XBC10HA-***-*** XBC15HA-***-*** XBC25HA-***-*** XBC45HA-***-*** XBC55HA-***-*** XBC65HA-***-*** Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 7: Dimensions (Mm)

    2 attenuator flange connections are attached to every unit. Add 60mm to dimension 'A' to include both flanges for standard (no roof) units. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 8 HE - Denotes the type of silencer required for the extract or intake. *Note: XBC15 silencers are also suitable for XBC10 units. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 9: Unit Installation

    •Fix brackets to drop rods to support attenuators •Use the 2 x Ø5.3mm holes on the attenuator brackets to position attenuator and fix self tapping screws in position. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 10 Silencers Belimo SM24A-S drive open/drive close actuator complete with switch. Motorised Damper Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 11: Switch Wiring

    After you have installed the hoses, it is essential to check them for tightness of fit at the connection points and to make sure that they run without any kinks. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 12 Unit operation will otherwise be unaffected. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 13: Setting To Work

    Default IP address: 192.168.11.12 Subnet mask: 255.255.255.0 LAN 011, node 012 Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 14: Connection Chart

    5.7.3 Conductor Removal Insert an operating tool in to the operating slot to remove the conductor, just like the original CAGE CLAMP® terminals blocks. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 15 H) Fresh air temperature Extract fan (drive & health) 5.9 I/O Damper Wiring Diagram - 24V Actuator (e.g. XBC15-MD-AT) I/O Damper Wiring Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 16 Installation Manual XBC+ with Adapt Trend (T) Control 5.10 Basic Unit Connection Diagram Basic Unit Connection Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 17 Installation Manual XBC+ with Adapt Trend (T) Control 5.11 Controller Layout Diagram Controller Layout Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 18 XBC+ with Adapt Trend (T) Control 5.12 Wiring Diagrams 5.12.1 Unit Sizes 10-15 with No / LPHW Heating Sizes 10-15 with No / LPHW Heating Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 19 XBC+ with Adapt Trend (T) Control 5.12.2 Unit Sizes 25-65 with No / LPHW Heating Sizes 25-65 with No / LPHW Heating Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 20 Installation Manual XBC+ with Adapt Trend (T) Control 5.12.3 Unit Sizes 10-15 with Electric Heating Sizes 10-15 with Electric Heating Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 21 Installation Manual XBC+ with Adapt Trend (T) Control 5.12.4 Unit Sizes 25-65 with Electric Heating Sizes 25-65 with Electric Heating Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 22 CO2 setpoint. The target CO2 sensor setpoint Maintenance alarms are not covered by warranty. can be changed as one of the commissioning setpoints. Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 23 Set night cooling mode as active Off / On SUMMERNIGHTFREECOOLMINTEMP Night cooling lower cut-off temperature 5°C to 30°C SUMMERNIGHTFREECOOLFANSPEED Night cool fan speed 20 to 100 % Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 24 •Easy To Wire •Universal Kit Option For Retrofit Of Immersion Sensors •Adjustable Insertion Depth Flange Option For Duct Sensors Thermistor Temperature Sensors Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 25 •Quarter Turn Quick Release Lid (Duct Sensor) •Two Part Terminals To Facilitate Wiring •24V AC/DC Supply •Adjustable Depth Duct Mounting Flange Option Occupancy Sensors Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 26: Maintenance

    •Cardboard packaging, wood, used filters and other paper components can be largely recycled or fully processed in energy Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...
  • Page 27 Installation Manual XBC+ with Adapt Trend (T) Control NOTES Nuaire | Western Industrial Estate | Caerphilly | CF83 1NA | nuaire.co.uk 08. 12. 21. Document Number 671949...